Ingersoll-Rand X41 technical manual Installation

Models: X41

1 85
Download 85 pages 12.85 Kb
Page 6
Image 6

SECTION 4 — INSTALLATION

It is recommended that installation and commissioning be carried out by an authorized and trained product supplier.

UNIT LOCATION

The X4I can be mounted on a wall using conventional bolts. The X4I can be located remotely from the compressors as long as it is within 330 feet (100 meters) of cable length. The X4I must also be located within 330 feet (100 meters) of the system pressure transducer.

Dimensions

SPECIFICATIONS

11.45” x 9.45” x 6.0”

Weight

291mm x 241mm x 152mm

14lb (6.4kg)

Mounting

Wall, 4 x screw fixings

Enclosure

IP65, NEMA 4

Supply

230Vac +/- 10%, 50 Hz

Power

115Vac +/- 10%, 60 Hz

50VA

Temperature 32°F to 115°F

Humidity

(0°C to 46°C)

0% to 95% RH

 

(non-condensing)

Ingersoll Rand Automation

Model X4I

COMPRESSOR CONTROL CABLE

7 Conductor Cable, 18 Gauge, Stranded, Earth Shielded

OR

Single Conductor Wire, 18 Gauge Stranded, Quantity (7)

In Grounded Conduit

No Greater Than 330FT (100M)

24VAC Control Voltage

Compressor #4 Control Cable

Local Disconnect (Breaker) Box

On/Off

 

 

 

 

 

 

Compressor #3 Control Cable

Fused for 50VA

 

Supply Voltage Cable

 

Compressor #2 Control Cable

Power Cable

 

Switch

 

 

 

 

 

 

 

Compressor #1 Control Cable

 

3 conductor (L, N, E)

 

 

 

 

 

 

(Sized in accordance with local

 

 

 

 

 

 

 

 

 

electrical and safety regulations).

Pressure Transducer Cable

Compressor

IR-PCB

 

 

Reference X4I Compressor

 

 

 

Interconnect and Application Guide

 

 

 

 

 

 

 

 

 

 

#1

 

 

 

For Connections Between The

PRESSURE TRANSDUCER CABLE

 

 

Compressor #1 Control Cable

 

 

Compressor And The IR-PCB

2 Conductor Cable, 18 Gauge Stranded

 

X4I X01 CONNECTOR

IR-PCB CONNECTOR

 

 

 

 

 

 

V1

 

V1

 

 

 

 

Earth Shielded

 

 

 

 

 

 

 

 

 

1

 

1

 

 

 

 

No Greater Than 330FT (100M)

 

 

2

 

2

 

 

 

 

24VDC Control Voltage

 

 

3

 

3

 

Compressor

IR-PCB

 

 

4

 

4

 

 

 

 

 

 

 

 

#2

 

X4I X05 CONNECTOR

PT CONNECTOR

 

 

5

 

5

 

 

 

 

 

6

 

6

Compressor #2 Control Cable

25

+VDC Pin #3

 

 

 

 

 

 

 

 

 

 

X4I X02 CONNECTOR

IR-PCB CONNECTOR

26

Signal Pin #1

 

 

 

 

 

V3

 

V1

 

Reference X4I Operations Manual for Pressure

 

 

 

 

 

7

 

1

 

Sensor Connection Details

 

 

 

 

 

8

 

2

 

 

 

 

 

 

9

 

3

 

 

 

 

 

 

 

 

10

 

4

 

 

PRESSURE TRANSDUCER

 

 

 

 

11

 

5

 

 

 

 

 

 

12

 

6

 

 

Compressor IR-PCB

RECEIVER

#3

 

 

Compressor #3 Control Cable

 

X4I X03 CONNECTOR

IR-PCB CONNECTOR

 

V3

 

V1

131

 

14

2

 

 

 

 

15

3

Compressor

IR-PCB

 

16

4

 

 

#4

 

 

17

5

 

 

DRIP LEG

18

6

Compressor #4 Control Cable

 

 

 

 

 

X4I X04 CONNECTOR

IR-PCB CONNECTOR

 

 

 

V4

 

V1

 

 

 

19

 

1

 

 

 

20

 

2

 

 

 

21

 

3

 

 

 

22

 

4

 

 

 

23

 

5

 

 

 

24

 

6

www.air.irco.com

6

X4I System Automation

 

Page 6
Image 6
Ingersoll-Rand X41 technical manual Installation