Co-linear Hearthmount Installation

The Jøtul GF 200 DV Lillehammer may be vented through a masonry fireplace using Simpson Dura- Vent Chimney Liner Conversion Kit 923GK. When installed in the manner described below, this system can improve the performance of the appliance in cold climate situations, as well as simplify the vent installation.

These guidelines must be followed:

Exhaust Gases

#923GK

Maximum Co- Top Kit Linear Height

- 35 FT

#991

High

Wind Cap

Intake Air

1.

Prior to the installation, the chimney flue must be

 

thoroughly cleaned and inspected by a qualified

 

chimney service person.

2.

In a masonry chimney, a fireclay liner or listed

 

steel liner, must be present the entire length of

 

the chimney.

3.

No appliance can be installed into a chimney flue

 

serving any other appliance of any kind.

4.

The minimum length of the AIR INTAKE FLEX is 6

Minimum Co-

Linear Height

-10 FT

feet- measured off of the back of the appliance

and IT MUST EXTEND PAST THE DAMPER AREA OF

THE FIREPLACE.

5. If the intake flex does not extend the full length

of the chimney and connect to both the unit and

the termination cap, A METAL BLOCK OFF PLATE

MUST BE CONSTRUCTED AND INSTALLED ABOVE

THE UNIT PRIOR TO THE END OF THE INTAKE FLEX

AND MUST COMPLETELY SEAL THE CHIMNEY FLUE

FROM THE ROOM.

Consult with the local code authority having jurisdiction before proceeding with this type of installation.

Refer to the vent manufacturer’s instructions for specific installation requirements.

Air Intake flex pipe must extend a minimum of 6 ft. and through the damper area.

Chimney must be sealed off from the room by a steel plate at the damper area.

Dual 3” Flex Liners

WARNING: FAILURE TO POSITION THE PARTS AND STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED FOR USE WITH THIS APPLIANCE MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY. BE SURE TO MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES AS DEFINED IN THIS MANUAL AND INM THE INSTRUCTIONS PROVIDED WITH EACH VENT

COMPONENT.

IMPORTANT NOTICE

THE USE OF AN EXISTING CHIMNEY AS AN AIR INTAKE IS NOT COVERED UNDER THE ANSI Z21.88-1999-CSA 2.33-M99

TEST METHODS AND RESULTING ITS/WHI PRODUCT CERTIFICATION. THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR TO PRO- CEEDING WITH THIS INSTALLATION

#923GCL Co- Linear Appliance Adaptor

Figure 8. Co-Linear Vent System installed in a masonry fireplace.

21 1/2”

(546mm)

18”

(457 mm)

Figure 9. Co-Linear Adaptor dimensions with Plinth legs.