Horizontal Venting (Horizontal Termination)

The maximum horizontal run made directly off the rear of the stove into a standard horizontal cap (#984 or #985) must be no more than a 9” section of Simpson Dura-vent (#907B). See Figure 12-1.

The maximum horizontal run made directly off the rear of the stove into a 14” snorkel cap (#982) must be no more than a 24” section of Simpson Dura-vent (#904). See Figure12-3.

The horizontal termination cap must maintain a 3" clearance (80 mm) to any overhead combus- tible projections 2 1/2" (60 mm) or less. Maintain 12" (300 mm) clearance from projections exceed- ing 2 1/2". See Figure 13.

Any horizontal run of vent must be level or have a 1/4" (5 mm) rise for every foot (300 mm) of run toward the termination cap. DO NOT ALLOW THE VENT TO RUN DOWNWARD, AS THIS CAN CAUSE HIGH TEMPERATURES AND THE POSSIBILITY OF A FIRE.

A 1” (26 mm) clearance must be maintained around all co-axial vent pipe.

For buildings with vinyl siding, a Vinyl Siding Standoff should be installed between the vent cap and the exterior wall (Simpson Dura-Vent #950). The Standoff prevents exposure of the vinyl siding to excessive heat that can damage the siding material.

A 10" X 10" (250 mm x 250 mm) square hole is required to maintain proper vent clearances through a combustible wall. Simpson Dura-Vent Wall Thimble #942 installed according to the manufacturer’s instructions meets clearance requirements.

DO NOT FILL AIR SPACE WITH ANY TYPE OF INSULATION.

Do not recess the termination cap into the exterior wall or siding.

OPTION # 1

 

 

 

 

10” Max.

 

 

 

250 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Simpson Dura-Vent

Horizontal Termination

Cap #984 or #985

9” (230 mm) Max. Horizontal Simpson Dura-Vent #907B No Draft Restriction Required

Figure 12-1. Maximum horizontal run to rear termination.

OPTION # 2

 

 

 

 

 

5” Max.

 

 

 

 

 

 

 

 

 

 

130 mm

 

 

 

 

 

 

 

 

 

 

 

Simpson Dura-Vent

Horizontal Termination

Cap #984 or #985

6” (150 mm) Min. Horizontal Simpson Dura-Vent #908B No Draft Restriction Required

Figure 12-2. Minimum horizontal run to rear termination.

OPTION # 3

Simpson Dura-Vent

 

14” Snorkel

 

Termination #982

24” (610 mm) Max. Horizontal Run into 14” Snorkel,

Simpson Dura-Vent #904

Both Draft Restrictors Required

Figure 12-3. Maximum horizontal run to a snorkel termination.

IMPORTANT:

FOLLOW THE INSTALLATION IN-

STRUCTIONS PROVIDED WITH EACH SIMPSON DURA-VENT COMPONENT.

12

Page 12
Image 12