Jotul GF 200 DV Clearance to Combustibles, Minimum Stove Clearance, Minimum Vent Pipe Clearance

Models: GF 200 DV

1 28
Download 28 pages 892 b
Page 7
Image 7
Clearance to Combustibles

Clearance to Combustibles

Minimum Stove Clearance

Rear

0”

(0mm)

Ceiling

17”

(432mm)

Corner

2”

(51mm)

Right Side

2”

(51mm)

Left Side

*10”

(255mm)

*Necessary for complete access to pull out required Lighting Instructions Plate.

Minimum Vent Pipe Clearance

Horizontal runs:

Off the top of the pipe -

2” (26mm)

Off the sides and bottom -

1” (26mm)

Vertical runs:

 

 

All sides

-

1” (26mm)

See Figures 4 and 5.

Mantel and Trim Clearances

24”or greater depth

 

or ceiling

 

 

12” or less

17”

 

6” or

 

less

432 mm

 

 

 

10”

 

2”

255 mm

 

6”

51 mm

 

 

153 mm

1” deep

 

 

trim

 

 

must be

 

 

2” off

 

 

the top of

 

 

the

 

 

stove.

Figure 3. Mantel / Trim Clearances

Parallel Installation

Rear Wall Clearance: 0” (ZERO mm)

Max.

Alcove

Depth

24”

610

mm

Left Side*

 

 

Right

 

 

2”

 

 

 

 

 

 

10”

 

 

 

 

 

 

 

 

 

25

 

 

 

 

 

 

230 mm

 

 

Side

 

 

 

 

 

 

mm

 

 

 

 

 

 

 

*Allow 10” on left side of the appliance for complete access to the lighting instructions and control valve.

Figure 4. Clearances with stove parallel to the walls

Alcove Installation

Maximum Depth:

24”

(610mm)

Minimum Width:

35”

(890mm)

Minimum Ceiling Height:

42”

(1067mm)

Corner Installation

2”

51mm

2”

51mm

Figure 5. Clearance to rear corners.

7

Page 7
Image 7
Jotul GF 200 DV Clearance to Combustibles, Minimum Stove Clearance, Minimum Vent Pipe Clearance, Parallel Installation