Masonry or Prefabricated Chimney Conversion

The GF200 DV Lillehammer is approved for use with Simpson Dura-vent Chimney Kit #934 in a masonry chimney or a prefabricated solid fuel listed chimney. These installation requirements must be followed:

1.In masonry chimney, a fireclay liner or listed steel liner, must be present the entire length of the chimney.

2.The liner must have an inside dimension of 6” round or greater. (USE KIT #934)

3.Prefabricated chimneys must be UL 103 or ULC S- 629 listed and have a minimum INSIDE diameter of 6 inches, (150 mm). Prefabricated chimneys must be listed for the specific Simpson Dura-Vent Chimney Conversion Kit. (USE KIT #931, #932, or #933)

4.The Exhaust Restrictor plate, shipped with the stove, must be installed according to the instruc- tions on page 8.

Exhaust Gas

Cap Adaptor- included in #934 Kit

4” Flex Pipe not included in kit

Support/Wall Thimble Cover - included in#934 Kit

#991 Vertical

Termination Cap

Intake Air

Use Standard Simpson Dura-Vent GS Pipe from stove to thimble

IMPORTANT NOTICE

THE USE OF AN EXISTING CHIMNEY AS AN AIR INTAKE IS NOT COVERED UNDER THE ANSI Z21.88-1999-CSA

Figure 10. Vent System through a masonry chimney using the Simpson Dura-Vent Chimney Conversion Kit #934. May also be used in listed prefabricated chimneys. Drawing is for illustrative purposes only - DO

NOT VENT TWO APPLIANCES INTO A SINGLE CHIMNEY.

Horizontal Overhang

2.33-M99 TEST METHODS AND RE-

SULTING ITS/WHI PRODUCT CERTIFI- CATION. THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR TO PROCEEDING WITH THIS INSTALLATION METHOD.

WARNING:

2 ft. min.

Termination

Cap

2 ft.

Wall

min.

 

cal

 

 

 

 

 

Verti

2ft.

min.

12

Lowest

Discharge

Opening

X

Roof Pitch

is X / 12

FAILURE TO POSITION THE PARTS AND STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED WITH THIS APPLIANCE MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY. BE SURE TO MAINTAIN THE PROPER CLEARANCES TO COMBUS- TIBLES AS DEFINED IN THIS MANUAL AND IN THE INSTRUCTIONS PROVIDED WITH EACH SIMPSON DURA-VENT COMPONENT.

2 ft. = minimum height from roof to lowest discharge opening

ROOF SLOPE

Minimum

Height above Roof

Flat to 6/12

1’ 0”

0.3 M

Over 7/12 to 9/12

2’ 0”

0.6 M

Over 10/12 to 12/12

4’ 0”

1.2 M

Over 13/12 to 16/12

6’ 0”

1.8 M

Over 17/12 to 21/12

8’ 0”

2.4 M

Figure 11. Gas Vent Height Rule: Vertical vent termination height above roof.

11

Page 11
Image 11
Jotul GF 200 DV manual Masonry or Prefabricated Chimney Conversion, Not Vent TWO Appliances Into a Single Chimney