8 Inspections
4.0 INSPECTIONS

4.1 External Inspections

1. While the UPS system is still on th e truck, inspect the equipment and shippi ng container(s)
for any signs of damage or mishan dling. Do not attempt to install the system if damage is
apparent. If any damage is noted, file a damage claim wi th the shipping agency within 24
hours and contact Liebert Global Services at 1-800-543 -2378 to inform them of the damage
claim and the condition of the equipment.
2. Locate the bag containing the keys for the front access door. The bag is attached to the
cabinet.
3. Compare the contentsof the shipment with the bill of lading. Report any missing itemsto the
carrier and to Liebert Global Services immediately.
4. Check the nameplate on the cabinets to verify that the model numbers correspondwith the
one specified. Recordthe model numbers and serial numbers in the front of this installation
manual. A record of this information is necessary should servicing become required.

4.2 Internal Inspections

1. Verify that all items have been received.
2. If spare parts were ordered, verify arrival.
3. Open doors and removecabinet panels to check for shipping damage to internalcomponents.
4. Check for loose connections or un secured components in the cabinet(s).
5. Check for installationof circuit breaker line safety shields. There should be no exposed circuit
breaker terminalsw henthe cabinet doors are opened.
6. Check for any unsafe condition that may be a potential safety hazard.
7. UPS modules are shipped with internally mounted shipping brac kets. The shipping brackets
(painted orange) must be removed from the rear (remove rear panels).