12.0APPENDIX A - SITE PLANNING DATA
500-750kVA Multi-Module Systems
12.1Notes
1.Nominal rectifier AC input current (considered continuous) is based on full rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current limit are defined in NEC 100. Maximum input current is controlled by current limit setting which is adjustable. Values shown are for maximum setting of 125%. Standard factory setting is 115%.
2.Nominal AC output current (considered continuous) is based on full rated output load. Maximum current includes nominal output current and overload for 10 minutes.
3.Bypass AC input current (considered continuous) is based on full rated output load.
4.Feeder protection (by others in external equipment) for rectifier AC input and bypass AC input is recommended to be provided by separate overcurrent protection devices.
5.UPS output load cables must be run in separate conduit from input cables.
6.Power cable from module DC bus to battery should be sized for a total maximum 2.0 volt line drop (measured at the module) at maximum discharge current.
7.Grounding conductors to be sized per NEC
8.Rectifier AC Input:
AC Output, SCC to Load:
Bypass AC Input:
Module DC Input from Battery:
9.All wiring is to be in accordance with National and Local Electrical Codes.
10.Minimum clearance is 2 feet above UPS.
11.Top or bottom cable entry through removable access plates. Cut plate to suit conduit size.
12.Control wiring and power cables must be run in separate conduits. Control wiring must be stranded tinned conductors.
13.7% maximum input harmonic current and 0.92 lagging input power factor at full load with 6- pulse rectifier and optional input filter (4% with
30% maximum input harmonic current and 0.85 lagging input power factor at full load without optional input filter (9% with
14.Dimensions and weights do not include the System Control Cabinet required for Multi- Module Systems.
80 Appendix A - Site Planning Data