82 Appendix A - Site Planning Data

Table 5 Series 600T Multi-Module Systems, 500-750 kVA - 600 VoltInp ut
UPS
Rating AC
Output
Voltage
Options
Rectifier
AC
Input
Current
Inverter
or
Bypass
AC Output
Current
Required
Battery
Discon-
nect
Rating
Maximum
Battery
Current
at End of
Discharge
Maximum
HeatDis-
sipation
BTU/hr.
Dimen-
sions
Inches
Approx.
Weight
Lb.
Floor
Loading
Lb./
Sq.ft.
kVA kW Input
Filter Input
Xfmr Nom Max Nom Max Amps Amps Full
Load (WxDxH) (Un-
packed)
(Concen-
trated
Loading)
500 400 600 NO NO 484 6 05 481 601 1,000 1,079 94,900 72x39x79 6,110 313
500 400 600 YES NO 449 56 1 481 601 1 ,000 1,0 79 99,600 72x39x79 6,310 324
500 400 600 NO YES 490 612 481 601 1,000 1,079 110,700 96x39x79 8,710 355
500 400 600 YES YES 454 567 481 601 1,000 1,079 115,500 96x39x79 8,910 343
500 450 600 NO NO 545 6 81 481 601 1,200 1,214 106,750 72x39x7 9 6,130 314
500 450 600 YES NO 505 631 481 601 1,200 1,214 112,050 72x39x79 6,330 325
500 450 600 NO Y ES 551 6 88 481 601 1,200 1,214 124,550 96x39x7 9 9,030 347
500 450 600 YES YES 510 638 48 1 601 1,200 1,214 12 9,950 96x39x79 9,230 355
625 500 600 NO NO 602 7 53 601 752 1,400 1,349 108,950 108x39x79 7,805 300
625 500 600 YES NO 559 699 601 752 1,400 1,349 118,650 108x39x79 8,025 309
625 500 600 NO Y ES 609 761 601 752 1,400 1,349 128,450 12 0x39x79 10,485 323
625 500 600 YES YES 554 705 60 1 752 1,400 1,349 13 4,400 12 0x39x79 10,705 329
750 600 600 NO NO 723 9 03 722 902 1,600 1,619 130,700 108x39x79 8,405 323
750 600 600 YES NO 671 83 9 722 90 2 1,600 1, 619 142,350 108x39x79 8,625 332
750 600 600 NO Y ES 730 913 722 902 1,600 1,619 154,150 12 0x39x79 11,485 353
750 600 600 YES YES 677 846 72 2 902 1,600 1,619 16 1,250 120x 39x79 11,705 360
750 67 5 600 NO Y ES 822 102 7 722 90 2 1,600 1,822 173,400 120x39x79 11,785 363
750 675 600 YES YES 762 952 72 2 902 1,600 1,822 18 1,400 12 0x39x79 12,005 369
Applicable
Notes: 13 — 1,4,5,7,8,
9,11,12 2,3,5,7,8,
9,11,12 6 6,8,9,
11,12 —1414
Forexplanation of notes, seereferenced numbers in 12.1 - Notes