Installation & Service Manual
1 Determine unit location
Installation
This unit meets the safe lighting performance criteria with the gas manifold and control assembly provided, as specified in the ANSI standards for
Locating the unit
1.Maintain all clearances from combustible construction when locating unit. See Clearances from Combustible Construction, this page.
2.Locate the unit so that if water connections should leak, water damage will not occur. When such locations
cannot | be avoided, install a | suitable | drain | pan that | |
is | the | unit. The pan must not | |||
restrict | combustion | air | flow. | The | appliance |
manufacturer is not responsible for water damage in connection with this unit, or any of its components.
3.Install indoor units so that the ignition system components are protected from any water while operating or during service.
4.Appliances located in a residential garage and in adjacent spaces that open to the garage and are not part of the living space of a dwelling unit must be installed so that all burners and burner ignition devices
have | a | minimum | clearance of | not | less |
than | 18'' | (46cm) | above the | floor. | The |
appliance must be located or protected so that | it is | ||||
not subject to physical damage by a moving vehicle. |
|
5. | DO NOT install this appliance in any location where |
| gasoline or flammable vapors are likely to be present. |
6. | The appliance must be installed on a level surface. |
7. | Models 497 - 747 are approved for installation on |
| combustible flooring using the approved combustible floor |
| kits (reference Table 1A). Models 987 - 2067 are approved |
| for installation on combustible flooring. Do not install |
| appliances directly on carpeting. |
8. | For outdoor models, you must install an optional vent |
| kit. Instructions for mounting the vent kit are included |
| in the venting section. Do not install outdoor models |
| directly on the ground. You must install the outdoor |
| unit on a concrete, brick, block, or other |
Indoor clearances from combustible construction
Maintain minimum specified clearances for adequate operation. Allow sufficient space for servicing pipe connections, pump and other auxiliary equipment, as well as the unit. See rating plate for specific service clearance requirements.
Right Side | 3'' (7.5 cm) |
Rear | 3'' (7.5 cm) (3'' min. from any surface)* |
Left Side | 6'' (15 cm) (24'' (0.61 m) suggested for |
| service) |
Front | Alcove* (30'' (0.76m) suggested for service) |
Top | 3'' (7.5 cm) |
Flue | 1'' (25.4 mm) |
Hot Water Pipes 1'' (25.4 mm)
*An Alcove is a closet without a door.
Note: No additional clearance is needed on the right side of the unit for the observation port. An observation port is located on both the right and left side of the unit.
Figure
3" |
|
|
| 3" | |
MIN |
|
|
|
| MIN |
REAR |
|
|
|
| TOP |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
special location and clearance requirements. See |
Outdoor Installation Venting, page 20. A wind proof |
cabinet protects the unit from weather. |
6"
MIN
LEFT SIDE
3"
MIN
RIGHT SIDE
30"
MIN FRONT
10