Lochinvar 497 - 2067 service manual Determine unit location, Installation, Locating the unit

Models: 497 - 2067

1 68
Download 68 pages 11.45 Kb
Page 10
Image 10
1 Determine unit location

Installation & Service Manual

1 Determine unit location

Installation

This unit meets the safe lighting performance criteria with the gas manifold and control assembly provided, as specified in the ANSI standards for gas-fired units. ANSI Z21.13/CSA 4.9 and ANSI Z21.10.3/CSA 4.3.

Locating the unit

1.Maintain all clearances from combustible construction when locating unit. See Clearances from Combustible Construction, this page.

2.Locate the unit so that if water connections should leak, water damage will not occur. When such locations

cannot

be avoided, install a

suitable

drain

pan that

is well-drained under

the

unit. The pan must not

restrict

combustion

air

flow.

The

appliance

manufacturer is not responsible for water damage in connection with this unit, or any of its components.

3.Install indoor units so that the ignition system components are protected from any water while operating or during service.

4.Appliances located in a residential garage and in adjacent spaces that open to the garage and are not part of the living space of a dwelling unit must be installed so that all burners and burner ignition devices

have

a

minimum

clearance of

not

less

than

18''

(46cm)

above the

floor.

The

appliance must be located or protected so that

it is

not subject to physical damage by a moving vehicle.

 

5.

DO NOT install this appliance in any location where

 

gasoline or flammable vapors are likely to be present.

6.

The appliance must be installed on a level surface.

7.

Models 497 - 747 are approved for installation on

 

combustible flooring using the approved combustible floor

 

kits (reference Table 1A). Models 987 - 2067 are approved

 

for installation on combustible flooring. Do not install

 

appliances directly on carpeting.

8.

For outdoor models, you must install an optional vent

 

kit. Instructions for mounting the vent kit are included

 

in the venting section. Do not install outdoor models

 

directly on the ground. You must install the outdoor

 

unit on a concrete, brick, block, or other

Indoor clearances from combustible construction

Maintain minimum specified clearances for adequate operation. Allow sufficient space for servicing pipe connections, pump and other auxiliary equipment, as well as the unit. See rating plate for specific service clearance requirements.

Right Side

3'' (7.5 cm)

Rear

3'' (7.5 cm) (3'' min. from any surface)*

Left Side

6'' (15 cm) (24'' (0.61 m) suggested for

 

service)

Front

Alcove* (30'' (0.76m) suggested for service)

Top

3'' (7.5 cm)

Flue

1'' (25.4 mm)

Hot Water Pipes 1'' (25.4 mm)

*An Alcove is a closet without a door. Thirty-six inches (36") to rear required for outdoor installation.

Note: No additional clearance is needed on the right side of the unit for the observation port. An observation port is located on both the right and left side of the unit.

Figure 1-1_Indoor clearances from combustible construction

3"

 

 

 

3"

MIN

 

 

 

 

MIN

REAR

 

 

 

 

TOP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

non-combustible pad. Outdoor models have additional

special location and clearance requirements. See

Outdoor Installation Venting, page 20. A wind proof

cabinet protects the unit from weather.

6"

MIN

LEFT SIDE

3"

MIN

RIGHT SIDE

30"

MIN FRONT

Installation 10 Locating the unit

Page 10