Combination gas valves

Installation & Service Manual

3 Gas connections

Combination gas valves

These units fire in multiple stages of burner input. Each stage of burner operation has a combination gas valve(s) to cycle the gas supply on and off and regulate gas to the burners. Each combination valve consists of a gas regulator and two valve seats to meet the requirements for redundant gas valves. The valve has a gas control knob that must remain in the open position at all times when the unit is in service. The gas control valve has pressure taps located on the inlet and discharge sides of the valve. Manifold pressure is adjusted using the regulator located on the valve. A manifold gas pressure tap for each burner stick is located on the discharge side of the valve. The manifold pressure is preset at the factory and adjustment is not usually required. If you must adjust regulator pressure, follow the instructions under Gas Manifold Pressure Adjustment, page 25.

Venting of combination gas valves

The combination gas valve/regulator used on all units is equipped with an integral vent limiting orifice per ANSI Z21.78. The vent limiter ensures that the volume of gas emitted from the valve in the event of a failed gas diaphragm does not exceed the maximum safe leakage rate allowed by agency requirements.

Combination gas valve/regulators equipped with integral vent limiters are not required to have vent or relief lines piped to the outdoors. The termination of the vent limited opening on the combination gas valve/regulator complies with the safety code requirements of CSD-1, CF-190(a) as shipped from the appliance manufacturer without the installation of additional vent lines.

Checking gas supply pressure

Use the following procedure to check gas supply pressure.

1.Turn the main power switch to the “OFF” position.

2.Turn gas valve knobs to the “OFF” position.

3.Shut off gas supply at the field-installed manual gas cock in the gas piping to the unit. If fuel supply is L.P. gas, shut off gas supply at the tank.

4.Remove the 1/8'' hex plug, located on the “inlet” side of the gas valve (FIG. 3-3). You may also use a tapping on the field-installed main manual gas cock or gas piping. Install a fitting in the inlet pressure tapping suitable to connect to a manometer or magnehelic gauge. Range of scale should be 14'' w.c. or greater to check inlet pressure.

5.Turn on gas supply at the manual gas cock, turn on L.P. gas at the tank if required.

6.Turn the power switch to the “ON” position.

7.Turn the gas valve knobs to the “ON” position. Set the electronic temperature control or thermostat to call for heat.

8.Observe the gas supply pressure as all burners are firing. Ensure that inlet pressure is within the specified range. See Connecting To Gas Supply, page 22 for minimum and maximum gas supply pressures.

9.If gas pressure is out of range, contact gas utility, gas supplier, qualified installer or service agency to determine necessary steps to provide proper gas pressure to the control.

TABLE 3D

GAS PIPING SIZE CHART

Nominal

 

 

 

 

Length of Pipe in Straight Feet

 

 

 

 

 

Maximum

Iron Pipe

 

 

 

 

 

 

 

 

 

Capacity of Pipe

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in Thousands of

Inches

10

20

30

40

50

60

70

80

90

 

100

125

150

175

200

Btu/hr per hour

3/4

369

256

205

174

155

141

128

121

113

 

106

95

86

79

74

for gas pressures

 

of 14 Inches

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

697

477

384

328

292

267

246

256

210

 

200

179

164

149

138

Water Column

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(0.5 PSIG) or less

1 1/4

1,400

974

789

677

595

543

502

472

441

 

410

369

333

308

287

 

and a pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 1/2

2,150

1,500

1,210

1,020

923

830

769

707

666

 

636

564

513

472

441

drop of 0.5 Inch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water Column

2

4,100

2,820

2,260

1,950

1,720

1,560

1,440

1,330

1,250

 

1,180

1,100

974

871

820

 

(Based on NAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 1/2

6,460

4,460

3,610

3,100

2,720

2,460

2,310

2,100

2,000

 

1,900

1,700

1,540

1,400

1,300

 

GAS, 1025 Btu/hr

3

11,200

7,900

6,400

5,400

4,870

4,410

4,000

3,800

3,540

 

3,300

3,000

2,720

2,500

2,340

per Cubic Foot

 

of Gas and 0.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

23,500

16,100

13,100

11,100

10,000

9,000

8,300

7,690

7,380

 

6,870

6,150

5,640

5,130

4,720

 

Specific Gravity)

Venting of combination gas valves 24 Checking gas supply pressure