4 Water connections
Inlet and outlet connections
For ease of service, install unions on the water inlet and water outlet of the unit. The connection to the unit marked “Inlet” on the header should be used for return from the system. The connection on the header marked “Outlet” is to be connected to the supply side of the system.
Figure 4-1_Water Connections_Models 497 - 797
2" NPT WATER INLET
2" NPT WATER OUTLET
INSPECTION
PLUGS
Figure 4-2_Water Connections_Models 987 - 2067
INSPECTION
PLUGS
Relief valve
This unit is supplied with a relief valve(s) sized in accordance with ASME Boiler and Pressure Vessel Code, Section IV (“Heating Boilers”). The relief valve(s) is installed in the vertical position and mounted in the hot water outlet. No valve is to be placed between the relief valve and the unit. To prevent water damage, the discharge from the relief valve shall be piped to a suitable floor drain for disposal when relief occurs. No reducing couplings or other restrictions shall be installed in the discharge line. The discharge line shall allow complete drainage of the valve and line. Relief valves should be manually operated at least once a year.
CAUTION Avoid contact with hot discharge water.
Installation & Service Manual
Water flow switch
A water flow switch is factory installed in the outlet piping on all heating boilers and water heaters. The flow switch must prove water flow before a trial for ignition can begin. The flow switch requires a minimum flow of 15 - 18 GPM on Models 497 - 747 and 26 GPM on Models 987 - 2067 to make the flow switch and start burner operation. A water flow switch meets most code requirements for a low water cutoff device on boilers requiring forced circulation for operation.
Low water cutoff (if equipped)
If this boiler is installed above radiation level, a low water cutoff device must be installed at the time of boiler installation. An electronic low water cutoff is available as a factory supplied option on all models. The low water cutoff should be inspected every 6 months.
Heating boiler installations
Piping of the boiler system
The drawings in this section show typical boiler piping installations, see FIG.’s
CAUTION | The boiler system should not be operated at |
| less than 12 PSIG. |
|
Hot water piping must be supported by suitable hangers or floor stands, NOT by the boiler. Copper pipe systems will be subject to considerable expansion and contraction. Rigid pipe hangers could allow the pipe to slide in the hanger resulting in noise transmitted into the system. Padding is recommended on rigid hangers installed with a copper system. The boiler pressure relief valve must be piped to a suitable floor drain. See the Relief Valve section on this page.
CAUTION | A leak in a boiler “system” will cause the |
| “system” to intake fresh water constantly, |
| |
| which will cause the tubes to accumulate a |
| lime/scale build up. This will cause a non- |
| warrantable failure. |
27