Lochinvar 497 - 2067 Water connections, Installation & Service Manual, 3 1/2, Notice

Models: 497 - 2067

1 68
Download 68 pages 11.45 Kb
Page 32
Image 32
Manual background

Installation & Service Manual

4 Water connections

Figure 4-6_Primary/secondary piping of multiple boilers

COMMON MANIFOLD SIZE (Min.)

Models: 497 - 747

Number of Units

GPM

Diameter

(in.)

 

 

2

120

3 1/2

 

 

 

3

180

4

 

 

 

4

240

5

 

 

 

5

300

5

6

360

6

 

 

 

7

420

6

 

 

 

8

480

6

PRESSURE

RELIEF

VALVE

MAKE-UP

WATER

AIR

SEPARATOR

12" OR 4X PIPE DIAMETERS

FROM

SYSTEM

SECONDARY

BOILER

PUMP

COMMON MANIFOLD SIZE (Min.)

Models: 987 - 2067

Number of Units

GPM

Diameter

(in.)

 

 

2

180

4

 

 

 

3

270

5

 

 

 

4

360

6

5

450

6

 

 

 

6

540

6

 

 

 

7

630

8

8

720

8

 

 

 

EXPANSION

TANK

LOW WATER CUT-OFF (OPTIONAL)

TO SYSTEM

SYSTEM

PUMP

NOTICE

*Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.

Manual background 32 Manual background

Page 32
Image 32
Lochinvar 497 - 2067 service manual Water connections, Installation & Service Manual, 3 1/2, Notice