4 Water connections
Low temperature return water systems
Any
TABLE 4A
LTV VALVE KITS
MODEL | LTV VALVE KIT |
497 - 747 | VAL3048 |
987 - 2067 | VAL3047 |
Be sure to install the LTV valve per the piping diagrams included with the kits. Alternatively, a bypass as shown in FIG.
Condensation can cause operational problems, bad combustion, sooting, flue gas spillage and reduced service life of the vent system and related components. The bypass allows part of the boiler discharge water to be mixed with the cooler boiler return water to increase the boiler inlet temperature above 140°F (60°C). This should prevent the products of combustion from condensing in most installations. The bypass should be fully sized with a balancing valve to allow for proper adjustment. A valve must also be provided on the boiler discharge, after the bypass. Closing this discharge valve forces water through the bypass.
Installation & Service Manual
Start boiler adjustment with the bypass valve in the full open position and the boiler discharge valve half open. A small amount of the higher temperature boiler discharge water is mixed with the system water to maintain the desired lower system temperature. A remote low temperature range operator is recommended to control the boiler operation based on the lower system temperature. (See Terminal Strip Connection Options starting on page 38).
Radiant floor and snow melt heating systems
This type of heating boiler application operates in a low temperature range which requires a boiler bypass as described under the Low Temperature Bypass Requirements section. A
TABLE 4B
SYSTEM TEMPERATURE RISE CHART
Temperature Rise Based on Boiler Input in Btu/hr
Btu/hr | 10°F ΔT | 20°F ΔT | 30°F ΔT | 40°F ΔT | 50°F ΔT | 60°F ΔT | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Input | Output | GPM | Ft/hd | GPM | Ft/hd | GPM | Ft/hd | GPM | Ft/hd | GPM | Ft/hd | GPM | Ft/hd |
497,000 | 400,950 | 80+ | * | 40 | 4.0 | 27 | 1.6 | 20 | 0.6 | 16 | 0.6 | 13 | 0.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
647,000 | 522,450 | 129+ | * | 52 | 5.1 | 35 | 3.0 | 26 | 1.2 | 21 | 0.8 | 17 | 0.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
747,000 | 603,450 | 149+ | * | 60 | * | 40 | 4.0 | 30 | 1.6 | 24 | 1.2 | 20 | 0.7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
987,000 | 831,600 | 197+ | * | 80 | 5.2 | 53 | 2.4 | 40 | 1.4 | 32 | 1.0 | 27 | 0.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1,257,000 | 1,058,000 | 251+ | * | 102+ | * | 68 | 4.3 | 51 | 2.3 | 41 | 1.6 | 34 | 1.1 |
1,437,000 | 1,209,000 | 288+ | * | 116+ | * | 78 | 6.0 | 58 | 3.7 | 47 | 2.2 | 39 | 1.7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1,797,000 | 1,512,000 | 360+ | * | 146+ | * | 97+ | * | 73 | 6.2 | 58 | 4.2 | 49 | 2.4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2,067,000 | 1,738,800 | 414+ | * | 168+ | * | 112+ | * | 84 | 8.7 | 67 | 6.0 | 56 | 4.5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
+These flow rates exceed recommended flow rates of boiler. If these system temperature rises are used, an external piping bypass must be installed.
*These foot head calculations exceed the maximum allowable flow rate of the boiler. Requires
30