COMMON MANIFOLD SIZE (Min.)

Installation & Service Manual

7 Domestic water heaters (continued)

Figure 7-3_Multiple water heater piping with a single storage tank

COMMON MANIFOLD SIZE (Min.)

Models: 497 - 747

 

Number of Units

GPM

Diameter

(in.)

 

 

2

120

3 1/2

3

180

4

 

 

 

4

240

5

 

 

 

5

300

5

6

360

6

 

 

 

7

420

6

 

 

 

8

480

6

 

 

 

BUILDING

 

 

 

MIXING

 

 

HOT

 

 

 

VALVE

WATER

 

 

 

 

SUPPLY

 

 

 

 

RELIEF

VALVE

LOCK-TEMP

STORAGE

TANK

DRAIN

COMMON MANIFOLD SIZE (Min.)

Models: 987 - 2067

Number of Units

GPM

Diameter

(in.)

 

 

2

180

4

 

 

 

3

270

5

 

 

 

4

360

6

5

450

6

 

 

 

6

540

6

 

 

 

7

630

8

 

 

 

8

720

8

COLD

WATER

SUPPLY

MIN 4"

COMMON

MANIFOLD

SIZE

Manual background BUILDING

RETURN

NOTICE

*Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.