Lochinvar 497 - 2067 service manual A, Vent system options, Barometric damper location

Models: 497 - 2067

1 68
Download 68 pages 11.45 Kb
Page 17
Image 17
TABLE 2A

Installation & Service Manual

2 Venting (continued)

Figure 2-3_Vent termination from flat roof - 10 ft. or less from parapet wall

Figure 2-4_Vent termination from flat roof - 10 ft. or more from parapet wall

CAUTION

Units which are shut down or will not operate may experience freezing due to convective air flow in flue pipe, through the air inlet, or from negative pressure in the equipment room. In cold climates, operate pump continuously to help prevent freezing of boiler water. Provide proper freeze protection. See Freeze Protection, page 46.

TABLE 2A

FLUE PIPE SIZES

MODEL

FLUE SIZE

MODEL

FLUE SIZE

 

 

 

 

497

6''

1257

12''

647

8''

1437

12''

747

8''

1797

14''

987

10''

2067

14''

Installer may increase diameter one pipe size for ease of installation, if needed.

Vent system options

Vent System Options

This unit has two venting options.

1.Conventional Negative Draft Venting

This option uses a vertical rooftop flue termination.

Combustion air is supplied from the mechanical room. See page 15 for detailed information.

2.Outdoor Installation Venting

This option uses the installation of special air inlet and vent caps on the unit.

All units are shipped from the factory equipped for conventional negative draft venting. All other optional vent systems require the installation of specific vent kits and venting materials. The following is a detailed explanation of the installation requirements for each venting system, components used and part numbers of vent kits for each model.

Barometric damper location

Any venting system option that requires a barometric damper must adhere to the following directions for optimum performance. The preferred location for the barometric damper is in a tee or collar installed in the vertical pipe rising from the unit’s flue outlet. The barometric damper MUST NOT be installed in a bull head tee installed on the unit’s flue outlet. The tee or collar containing the barometric damper should be approximately three feet vertically above the connection to the unit’s flue outlet. This location ensures that any positive velocity pressure from the unit’s internal combustion fan is dissipated and the flue products are rising due to buoyancy generated from the temperature of the flue products. Adjust the weights on the damper to ensure that draft is maintained within the specified ranges.

Vent system options 17 Barometric damper location

Page 17
Image 17
Lochinvar 497 - 2067 service manual A, Vent system options, Barometric damper location