Image 9
Copper-fin Specifications

Installation & Service Manual

Ratings (continued)

Copper-fin Specifications

Model Number

 

 

 

 

Vent Size

 

Input

Water

Water Connections

Gas Connections

Note: Change “N” to

MBH

Content Gallons

 

 

(Note 1)

 

 

 

 

“L” for L.P. gas models

 

 

 

 

 

 

 

 

 

CWN497

495

1.7

2"

1 1/4"

6"

 

 

 

 

 

 

CWN647

645

2.0

2"

1 1/4"

8"

 

 

 

 

 

 

CWN747

745

2.1

2"

1 1/4"

8"

 

 

 

 

 

 

CWN987

985

2.2

2 1/2"

2"

10"

 

 

 

 

 

 

CWN1257

1255

2.6

2 1/2"

2"

12"

 

 

 

 

 

 

CWN1437

1435

2.9

2 1/2"

2"

12"

 

 

 

 

 

 

CWN1797

1797

3.3

2 1/2"

2"

14"

 

 

 

 

 

 

CWN2067

2065

3.6

2 1/2"

2"

14"

 

 

 

 

 

 

NOTICE Maximum allowed working pressure is located on the rating plate.

Notes:

1.Copper-fins require special gas venting. Use only the vent materials and methods specified in the Installation and

Service Manual.

2. The Copper-fin is orificed for operation up to 2000 feet altitude. The appliance will be derated 4% per 1000 feet above 2000 feet elevation. Consult the factory for installations above 2000 feet elevation.

HIGH ALTITUDE LABEL

Figure B High altitude label location_water heater