Installation & Service Manual
5 Electrical connections (continued)
Temperature adjustment
Note: The temperature controller is preset at the factory with test settings. You may need to adjust the settings to meet your specific needs.
WARNING Return water temperatures must not be less than 140°F. If lower return water temperatures
are required, follow the instructions for Low Temperature Return Water Systems on page 30.
Locating the temperature control
The temperature control is located behind the panel on the left front of the unit (see FIG.
1.Loosen the knurled knob at the bottom of the control panel cover.
2.Pull the bottom of the panel out and down to remove.
OJ1 |
OJ2 |
SETPOINT |
|
|
| |
| ||||
|
|
|
| OFFSET |
|
| DIFFERENTIAL |
|
|
|
|
|
OJ1
OJ2
Temperature control settings
There are three setting knobs on the temperature control unless your unit is specified as a boiler only with an outdoor air reset option. If your unit is a boiler only with an outdoor air reset option, there are additional controls for this option. They are explained under Outdoor Air Reset Option, page 40.
The three setting knobs on the temperature control are for Set Point, Differential, and
Maximum set point
The maximum set point for the control is factory set. Boilers are set to 230°F max., water heaters are set to 190°F max., and specialty state and local codes to 200°F.
These maximum set points are established by not cutting/ cutting the OJ1 and OJ2 jumpers located on the right side of the temperature controller (see FIG.
TEMPERATURE
CONTROL
TABLE 5B
Maximum Setpoint Determination
OJ1 | OJ2 | Max. | |
Setpoint | |||
|
| ||
|
|
| |
Connected | Connected | 230° | |
Cut | Connected | 190° | |
Connected | Cut | 200° | |
Cut | Cut | 160° |
NOTICE | Anytime that OJ1 is the only jumper cut, a |
new overlay is required under the Set Point | |
| knob on the temperature controller because |
| the scale has changed to a maximum of |
| 190°F. |
Anytime the OJ2 jumper is cut (with or without OJ1), a new overlay is required under the Set Point knob on the temperature controller because the scale has changed to a maximum of 200°F.