Lochinvar 497 - 2067 Combustion Air Options, Outside Combustion Air, No Ducts, One Opening

Models: 497 - 2067

1 68
Download 68 pages 11.45 Kb
Page 14
Image 14
Combustion Air Options

Installation & Service Manual

1 Determine unit location

Combustion Air Options

CAUTION Under no circumstances should a mechanical room ever be under a negative pressure.

Particular care should be taken when exhaust fans, clothes dryers, compressors, air handling units, etc., take away air from the inlet.

This unit has four combustion air options.

1. Outside Combustion Air, No Ducts

You can direct outside combustion air to this unit using either one or two permanent openings (see FIG. 1-5).

One Opening

The opening must have a minimum free area of one square inch per 3000 Btu input (7 cm2 per kW). You must locate this opening within 12'' (30 cm) of the top of the enclosure.

Two Openings

The combustion air opening must have a minimum free area of one square inch per 4000 Btu input (5.5cm² per kW). You must locate this opening within 12'' (30cm) of the bottom of the enclosure.

The ventilation air opening must have a minimum free area of one square inch per 4000 Btu input (5.5cm² per kW). You must locate this opening within 12'' (30cm) of the top of the enclosure.

Figure 1-6_Outside combustion air, two openings
Figure 1-5_Outside combustion air single opening

2. Outside Combustion Air, Using Ducts

You can direct outside combustion air to this unit using two air ducts to deliver the air to the boiler room.

Each of the two openings must have a minimum free area of one square inch per 2000 Btu input (11cm² per kW).

Figure 1-7_Outside combustion air, using ducts

1. Outside Combustion Air, No Ducts 14 One Opening

Page 14
Image 14
Lochinvar 497 - 2067 service manual Combustion Air Options, Outside Combustion Air, No Ducts, One Opening, Two Openings