Figure 1-1 Outdoor Air Reset Curve
Maximum SH set point
When the outdoor temperature drops to or below its minimum setting (F1) the water temperature will be at this point, if the SH set point is set higher (FIG.
Minimum SH set point
When the outdoor temperature rises to or above its maximum setting (F2) the water temperature will be at this point (FIG.
Outdoor air shutdown
When the outdoor temperature rises above this point, the control will block all SH demands (DHW demands will still be active). This parameter can be changed by the user or the installer by accessing parameter F5. The temperature range of this parameter is 0°F to 120°F. The default value is 80°F.
Outdoor air shutdown differential
The outdoor air shutdown differential parameter is the number of degrees below parameter F5 the outdoor air temperature must go before the boiler will respond to a SH demand. This parameter can be changed by the user or the installer by accessing parameter F6. The temperature range of this parameter is 0°F to 90°F. The default value is 10°F.
Shift reset curve
The shift reset curve parameter shifts the actual set point above the calculated set point the number of degrees in this parameter. This parameter can be changed by the installer by accessing parameter F7. The temperature range of this parameter is