Sequence of operation

Service Manual

1Service (continued)

Sequence of operation

Table 1A Sequence of operation - space heating and DHW

OPERATION

DISPLAY

 

 

 

1. Upon a call for heat, the control turns on the appropriate pumps

BLR: Standby

(system and boiler pumps for space heating call; DHW pump

OUT: 123.8F(129)

for DHW call).

 

 

 

 

 

 

 

 

 

2. The control connects 120 vac to the blower. The blower does

 

 

 

 

not run at this time.

 

 

 

 

• If the unit is equipped with a flow switch or low water cutoff, it

 

 

 

 

must close before the control powers up the blower.

 

 

 

 

• If the unit is equipped with a manual reset high limit it must be

BLR: Standby

closed before the control powers up the blower.

• If the unit is equipped with a solenoid valve and/or a vent

valve, they will be energized along with the blower.

OUT: 123.8F(129)

• If the unit is equipped with a gas pressure switch, it must close

 

 

 

 

at this time.

 

 

 

 

• If there is an auxiliary device connected to the unit, the unit

 

 

 

 

will then provide 24 vac to its enable relay. If the auxiliary

 

 

 

 

device has a proving switch, it must close before the

 

 

 

 

sequence continues.

 

 

 

 

 

 

 

3. The control then starts a 10 second prepurge cycle.

BLR: PREPURGE

 

OUT: 123.9F(129)

4. Once the prepurge cycle is complete, and the blocked drain

BLR: IGNITION

switch and auto-reset high limit are closed, the control starts

the 5 second trial for ignition by sending spark voltage to the

OUT: 123.9F(129)

spark electrode and opening the gas valve.

 

 

 

 

 

 

 

 

 

5. If the control does not detect flame by the end of the trial for

BLR: POSTPURGE, PREPURGE

ignition, the control performs a 10 second postpurge, another

prepurge and tries to light the burner again. If the burner does

OUT: 123.9F(129)

not light after 4 trials, the control locks out for 1 hour and then

 

 

 

 

tries another set of 4 trials.

 

 

 

 

 

 

 

 

 

6. If the control detects a flame before the trial for ignition ends, it

BLR: SH 20% RATE

begins to modulate the burner in order to maintain the set point.

If the boiler lights due to a space heating call for heat, and the

ramp delay function is active (default is off), the modulation

OUT: 124.8F(129)

will be held to a series of increasing limits after the burner has

 

 

 

 

lit.

 

 

 

 

 

 

 

 

 

7. If the space heating call for heat is active, and the DHW

BLR: DHW 85% RATE

thermostat closes, the control will turn on the DHW pump, wait

2 seconds, and then turn off the boiler pump. This will divert

the hot water away from the heating zone(s) and send it to the

OUT: 177.8(180)

DHW tank instead. The control will then modulate to maintain

 

 

 

 

the outlet temperature to the DHW boiler set point.

 

 

 

 

 

 

 

 

 

 

 

 