Service Manual

3Troubleshooting

Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

Temp O/Shoot

 

• Verify that the boiler pump is set to the proper speed

(continued)

 

or that the boiler pump is the proper size. Reference

(will require a manual

 

Section 6 - Hydronic Piping of the Knight Wall Mount

reset once the condition

Outlet water temperature has exceeded the

Installation and Operation Manual for boiler pump

has been corrected. Press

maximum outlet water temperature.

specifications.

 

the RESET button on the

 

 

 

SMART SYSTEM display

 

• Replace the main control board.

 

to reset.)

 

 

 

 

 

 

 

 

 

• Check set point of the external control.

 

Rem Ctrl Flt

External control is cycling too often.

• Check the wiring between the external control and the

unit.

 

 

 

 

 

 

• Replace the control.

 

 

 

 

 

Parameters

 

 

 

Progr

 

 

 

(will require a manual

After downloading parameters from a laptop,

• Press the ENTER/RESET button on

the SMART

reset once the condition

SYSTEM display panel.

 

the main control board must be reset.

 

 

 

has been corrected. Press

 

 

 

the RESET button on the

 

 

 

SMART SYSTEM display

 

 

 

to reset.)

 

 

 

 

 

 

 

 

• Check the wiring connections to switch. Wires should

 

 

be connected to the common and normally closed

 

 

terminals.

 

 

 

• Air intake lengths exceed the maximum allowed

 

 

lengths. Refer to Section 3 - General Venting of the

 

 

Knight Wall Mount Installation and Operation Manual

APS

 

for proper lengths.

 

 

 

 

Open

 

• Check for obstruction or blockage

in the air

(will require a manual

 

intake pipes or at terminations.

 

reset once the condition

Air pressure switch contacts are open.

• Check reference hoses connected to the air pressure

has been corrected. Press

 

the RESET button on the

 

switch for blockage or obstruction.

 

SMART SYSTEM display

 

 

 

to reset.)

 

• Inspect the burner. Reference page 26 of this manual

 

 

for removal and cleaning procedures. Replace if

 

 

necessary.

 

 

 

• Inspect the heat exchanger. Reference page 27 of this

 

 

manual for removal and cleaning procedures.

 

 

Replace if necessary.

 

 

 

• Faulty air pressure switch. Replace switch.

 

 

 

 

Rem Ctrl Flt 38 Parameters