Lochinvar 50-210 Troubleshooting continued, Fault, Description, Corrective Action, Service Manual

Models: 50-210

1 44
Download 44 pages 18.94 Kb
Page 39
Image 39
Service Blk

Service Manual

3Troubleshooting (continued)

Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

While the unit is in Service Mode, the outlet

• Establish a heating load to remove the heat from the

 

temperature has exceeded 185°F.

boiler loop.

 

 

• Verify that the system is full of water and that all air

 

 

has been properly purged from the system.

 

 

• Verify that the boiler is piped properly into the heating

 

 

system. Refer to Section 6 - Hydronic Piping of the

 

 

Knight Wall Mount Installation and Operation

 

 

Manual for the proper piping methods for the Knight

Service Blk

 

wall mount boiler.

 

 

• Check 120 vac to the boiler pump motor on a call for

 

 

heat. If voltage is not present, check the wiring back

 

 

to the main control board. Replace the main control

 

 

board if necessary.

 

 

• If 120 vac is present on a call for heat and the boiler

 

 

pump is not operating, replace the pump.

 

 

• Verify that the boiler pump is set to the proper speed

 

 

or that the boiler pump is the proper size. Reference

 

 

Section 6 - Hydronic Piping of the Knight

 

 

Boiler Installation and Operation Manual for boiler

 

 

pump specifications.

 

 

 

 

120 vac input to the main control board has

• Check 120 vac supply to the transformer.

 

dropped below 80 vac.

 

 

 

 

Low 24 vac

 

• Check wiring connections at the low voltage terminal

 

strip.

 

 

• Check the wire size/length to remote devices.

 

 

• Replace the transformer.

Watch Dog Error

The main control board has detected an

• Replace the main control board.

internal fault.

 

 

 

 

 

 

 

Write EEProm

The main control board has detected an

• Replace the main control board.

internal fault.

 

 

 

 

 

 

 

 

The main control board has detected an

• Replace the main control board.

CRC Parameters

internal fault.

 

 

 

 

 

 

 

 

The main control board has detected an

• Replace the main control board.

No Error Stored

internal fault.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

39

 

 

 

 

 

 

 

 

 

Page 39
Image 39
Lochinvar 50-210 Troubleshooting continued, Fault, Description, Corrective Action, Service Manual, Service Blk, Low 24 vac