Lochinvar 50-210 Description, Troubleshooting, Fault, Corrective Action, Flow, Switch/LWCO, Flame

Models: 50-210

1 44
Download 44 pages 18.94 Kb
Page 32
Image 32
DESCRIPTION

Service Manual

3Troubleshooting

Table 3F Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

Either the optional flow switch or the optional

• Check boiler pump operation on a call for heat.

 

low water cutoff is not making.

 

Flow

 

• Check for closed valves or obstructions in the boiler

 

piping.

Switch/LWCO

 

 

 

(will require a manual

 

• Verify system is full of water and all air has been

reset once condition has

 

purged from the system.

been corrected. Press

 

• Check for loose or misplaced jumpers if flow switch or

the RESET button on

 

 

LWCO is not installed.

the SMART SYSTEM

 

 

 

display to reset.)

 

 

Blown fuse.

• Replace fuse F2 on the control board, see page 28 of

 

 

 

this manual.

 

 

 

 

The blocked drain switch has detected

• Check condensate tube from unit to floor drain for

Blocked Drain SW

excessive condensate build up inside the

proper installation and obstructions.

(will require a manual

unit.

• Inspect condensate trap for blockage. Clean if

reset once condition has

 

 

necessary.

been corrected. Press

 

 

 

the RESET button on

 

• Check for loose wiring connection at wire harness

the SMART SYSTEM

 

plug.

display to reset.)

 

• Bad blocked drain switch. Replace switch.

 

 

 

 

 

Flame

The flame detector circuit is seeing a flame

• Check supply voltage for proper polarity.

Sequence

signal while no flame is present.

 

 

• Check external wiring for voltage feedback.

(will require a manual

 

 

 

reset once the condition

 

• Check the flame rod and make sure it is clean.

has been corrected.

 

• Check the internal wiring for bad connections.

Press the RESET button

 

on the SMART SYSTEM

 

• Replace main control board.

display to reset.)

 

 

 

 

 

 

GV/Relay

The main control board did not detect the gas

• Check wiring harness connection at the gas valve and

Fail

valve.

at the main control board.

 

 

 

(will require a manual

 

• Replace the gas valve wire harness.

reset once the condition

 

 

 

has been corrected.

 

• Replace the gas valve.

Press the RESET button

 

 

 

on the SMART SYSTEM

 

• Replace the main control board.

display to reset.)

 

 

 

 

 

 

32

Page 32
Image 32
Lochinvar 50-210 Description, Troubleshooting, Fault, Corrective Action, Flow, Switch/LWCO, Flame, Sequence, GV/Relay