Lochinvar 50-210 Troubleshooting, Fault, Description, Corrective Action, Service Manual, Fan High

Models: 50-210

1 44
Download 44 pages 18.94 Kb
Page 36
Image 36
Fan High

Service Manual

3Troubleshooting

Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

The actual fan RPM is 30% higher than what

• Vent/air intake lengths exceed the maximum allowed

 

is being called for.

lengths. Refer to Section 3 - General Venting of the

 

 

Knight Wall Mount Installation and Operation Manual

Fan High

 

for proper lengths.

 

 

OR

 

• Check for obstruction or blockage in the vent/air

Fan Speed High

 

intake pipes or at terminations.

(will require a manual

 

• Check the wiring connections at the fan and at the

reset once the condition

 

has been corrected. Press

 

main control board.

the RESET button on the

 

• Replace the fan.

SMART SYSTEM display

 

 

 

to reset.)

 

• Replace the main control board.

 

 

 

 

 

 

Either the inlet water or outlet water

• Check the sensors and their associated wiring.

Sensor Open

temperature sensor has been disconnected.

Repair or replace the sensor or wiring if damaged.

 

 

(will require a manual

 

• Measure the resistance of the sensors and compare

reset once the condition

 

 

the resistance to the tables on page 30 of this

has been corrected. Press

 

 

manual.

the RESET button on the

 

 

 

SMART SYSTEM display

 

• Replace the sensor if necessary.

to reset.)

 

 

 

 

 

 

 

Either the inlet water or outlet water

• Check the sensors and their associated wiring.

Sensor Shorted

temperature sensor has been shorted.

Repair or replace the sensor or wiring if damaged.

(will require a manual

 

• Measure the resistance of the sensors and compare

reset once the condition

 

 

the resistance to the tables on page 30 of this

has been corrected. Press

 

 

manual.

the RESET button on the

 

 

 

SMART SYSTEM display

 

• Replace the sensor if necessary.

to reset.)

 

 

 

 

 

 

Aux. Proving

An optional remote proving switch is not

• Check function of remote devices.

(will require a manual

making.

• Check for loose or misplaced jumper if auxiliary

reset once the condition

 

has been corrected. Press

 

proving switch is not installed.

the RESET button on the

 

 

SMART SYSTEM display

 

 

to reset.)

 

 

 

 

 

Fan Speed High 36 Sensor Open

Page 36
Image 36
Lochinvar 50-210 Troubleshooting, Fault, Description, Corrective Action, Service Manual, Fan High, Fan Speed High