Lochinvar 50-210 Troubleshooting continued, Fault, Description, Corrective Action, Service Manual

Models: 50-210

1 44
Download 44 pages 18.94 Kb
Page 37
Image 37
Temp O/Shoot

Service Manual

3Troubleshooting (continued)

Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

The stack temperature has exceeded the set

• Inspect the heat exchanger. Reference page 27 of

 

parameters for the boiler.

this manual for the procedure on how to clean the flue

 

 

 

 

side of the heat exchanger.

 

 

• Inspect the flue sensor and associated wiring.

 

 

Measure the resistance of the flue sensor and

 

 

compare to Table 3C on page 30 of this manual.

 

 

Replace the sensor if necessary.

 

 

• Verify that the vent/air intake pipes are properly

 

 

installed and that there are no obstructions.

 

 

• Replace the main control board.

 

 

 

 

The temperature rise across the heat

• Verify that the system is full of water and that all air

 

exchanger has exceeded the set parameters

has been properly purged from the system.

 

for the boiler.

 

 

 

 

 

 

 

• Verify that the boiler is piped properly into the heating

 

 

system. Refer to Section 6 - Hydronic Piping of the

 

 

Knight Wall Mount Installation and Operation Manual

 

 

for the proper piping methods for the Knight wall mount

 

 

boiler.

 

 

• Check for 120 vac to the boiler pump motor on a call

Temp O/Shoot

 

for heat. If voltage is not present, check the wiring

 

back to the main control board. Replace the main

 

 

 

 

control board if necessary.

 

 

• If 120 vac is present on a call for heat and the boiler

 

 

pump is not operating, replace the pump.

 

 

• Verify that the boiler pump is set to the proper speed

 

 

or that the pump is the proper size. Reference

 

 

Section 6 - Hydronic Piping of the Knight Wall Mount

 

 

Installation and Operation Manual for boiler pump

 

 

specifications.

 

 

 

 

Outlet water temperature has exceeded the

• Verify that the system is full of water and that all air

 

maximum outlet water temperature.

has been properly purged from the system.

 

 

• Verify that the boiler is piped properly into the heating

 

 

system. Refer to Section 6 - Hydronic Piping of the

 

 

Knight Wall Mount Installation and Operation Manual

 

 

for the proper piping methods for the Knight wall mount

 

 

boiler.

 

 

• Check for 120 vac to the boiler pump motor on a call

 

 

for heat. If voltage is not present, check wiring back

 

 

to the main control board. Replace the main control

 

 

board if necessary.

 

 

• If 120 vac is present on a call for heat and the boiler

 

 

pump is not operating, replace the pump.

 

 

 

 

 

 

 

 

 

 

37

 

 

 

 

 

 

 

 

 