Lochinvar 50-210 Troubleshooting continued, Fault, Description, Corrective Action, Auto Reset

Models: 50-210

1 44
Download 44 pages 18.94 Kb
Page 35
Image 35
Auto Reset

Service Manual

3Troubleshooting (continued)

Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

The outlet water temperature has exceeded

• Verify that the system is full of water and that all air

 

the fixed setting of the automatic reset high

has been properly purged from the system.

 

limit or the setting of an optional manual

• Verify that the boiler is piped properly into the heating

 

reset high limit.

system. Refer to Section 6 - Hydronic Piping of the

 

 

 

 

Knight Wall Mount Installation and Operation Manual

 

 

for the proper piping methods for the Knight wall

 

 

mount.

 

 

• Check 120 vac to boiler pump motor on a call for

 

 

heat. If voltage is not present, check wiring back to

 

 

the main control board.

 

 

• Replace the main control board if necessary.

Auto Reset

 

• If 120 vac is present on a call for heat and the boiler

 

pump is not operating, replace the pump.

High Limit

 

 

• If the system pump is a variable speed pump, ensure

 

 

 

 

that the system flow is not less than the boiler flow.

 

 

• If operating on something other than an outlet sensor,

 

 

check temperature setting of the main control board.

 

 

• If the optional manual reset high limit has tripped,

 

 

check setting of the device.

 

 

• Check resistance of water sensors and compare to

 

 

Table 3B on page 30 of this manual. Replace sensor

 

 

if necessary.

 

 

• Replace high limit.

 

 

 

 

The actual fan RPM is 30% lower than what

• Vent/air intake lengths exceed the maximum allowed

 

is being called for.

lengths. Refer to Section 3 - General Venting of the

 

 

Fan Low

 

Knight Wall Mount Installation and Operation Manual

 

for proper lengths.

OR

 

 

 

Fan Speed Low

 

• Check for obstruction or blockage in the vent/air

(will require a manual

 

 

intake pipes or at terminations.

reset once the condition

 

 

 

has been corrected. Press

 

• Check the wiring connections at the fan and at the

the RESET button on the

 

 

main control board.

SMART SYSTEM display

 

 

 

to reset.)

 

• Replace the fan.

 

 

 

 

• Replace the main control board.

 

 

 

 

Blown fuse.

• Replace fuse F4 on the control board, see page 28 of

 

 

this manual.

 

 

 