Service Manual
3Troubleshooting (continued)
Table 3E Troubleshooting Chart - Noisy System
FAULT |
| CAUSE | CORRECTIVE ACTION |
|
|
|
| ||
| - Supply gas problem. Natural gas pressures | • Refer to Section 7 - Gas Connections of the Knight | ||
| should be between 4 inches w.c. and | Wall Mount Installation and Operation Manual for | ||
| 14 inches w.c. | LP gas pressures should | detailed information concerning the gas supply. |
|
| be between | 8 inches w.c. and |
|
|
| 14 inches w.c. |
|
|
|
|
|
|
| |
| - Gas/air mixture problem. | • Refer to the Gas Valve Adjustment Procedure | on | |
|
|
| page 41 of this manual for the proper gas valve setting. | |
|
|
| Verify that the vent/air intake lengths do not exceed the | |
|
|
| maximum listed in the General Venting section of the | |
|
|
| Knight Wall Mount Installation and Operation Manual. | |
Noisy |
|
| ||
- Dirty/damaged burner. | • Refer to page 26 in this manual for the burner removal | |||
Operation |
|
| and inspection procedure. Clean or replace the burner | |
|
|
| as necessary. |
|
|
|
|
| |
| - Low water flow through the heat exchanger. | • Refer to Section 6 - Hydronic Piping of | the | |
|
|
| Knight Wall Mount Installation and Operation Manual for | |
|
|
| minimum flow rates. Verify that the boiler is piped in a | |
|
|
| primary/secondary fashion and that the boiler and | |
|
|
| system pump are running on a call for heat. |
|
|
|
|
| |
| - Air in the piping system. | • Properly purge all air from the piping system. |
| |
|
|
|
| |
| - Low system water pressure. | • Verify system pressure is a minimum of 12 psi. |
| |
|
|
|
| |
No Pump | - Blown fuse. |
| • Replace fuse F5 on the control board, see page 28 of | |
Operation - |
|
| this manual. |
|
Boiler Pump |
|
| Note: Make sure pump amperage does not exceed | |
System Pump |
|
| ||
|
| 1.8 amps. |
| |
or |
|
|
| |
|
|
|
| |
DHW Pump | - Faulty pump. |
| • Replace pump. |
|
|
|
| ||
|
|
|
| |
| - Internal fault on control board. | • Replace main control board. |
| |
|
|
|
| |
|
|
| ||
| - System pressure exceeds relief valve | • Lower the system pressure below the 30 psi rating of | ||
Relief Valve | setting. |
| the supplied relief valve or replace the standard relief | |
|
| valve with a higher rated valve up to the maximum | ||
Opening |
|
| pressure of the heat exchanger. |
|
|
|
| • Improperly sized expansion tank. |
|
|
|
|
|
|
31