Lochinvar 2072, 502 operation manual Gas connections continued, D, Checking gas supply pressure

Models: 2072 502

1 68
Download 68 pages 54.37 Kb
Page 33
Image 33
3 Gas connections (continued)

3 Gas connections (continued)

Combination gas valve/regulators equipped with integral vent limiters are not required to have vent or relief lines piped to the outdoors. The termination of the vent limited opening on the combination gas valve/regulator complies with the safety code requirements of CSD-1, CF-190(a) as shipped from the appliance manufacturer without the installation of additional vent lines.

Checking gas supply pressure

Use the following procedure to check gas supply pressure.

Installation & Operation Manual

13.Remove the manometer and related fitting from the “inlet” side of the gas valve, replace 1/8" hex plug in gas valve and tighten.

14.Turn on gas supply at the manual valve, turn on L.P. gas at the tank if required.

15.Turn the power switch to the “ON” position.

16.Turn the gas valve knob to the “ON” position.

17.Set the electronic temperature control or thermostat to call for heat.

1.

Turn the main power switch to the “OFF” position.

2.

Turn gas valve knobs to the “OFF” position.

3.

Shut off gas supply at the field-installed manual gas cock in

 

the gas piping to the unit. If fuel supply is L.P. gas, shut off

 

gas supply at the tank.

4.

Remove the 1/8" hex plug, located on the “inlet” side of the

 

gas valve. You may also use a tapping on the field-installed

￿WARNING

After completing any testing on the gas system, leak test all gas connections. Apply a soap/water solution to all gas connections while main burners are operating. Bubbles forming indicate a leak. Repair all leaks at once. Do not operate this unit with a leak in the gas train, valves or related piping.

 

main manual gas cock or gas piping. Install a fitting in the

 

inlet pressure tapping suitable to connect to a manometer

 

or magnehelic gauge. Range of scale should be 14" w.c. or

 

greater to check inlet pressure.

5.

Turn on gas supply at the manual gas cock, turn on L.P. gas

 

at the tank if required.

6.

Turn the power switch to the “ON” position.

7.

Turn the gas valve knobs to the “ON” position. Set the

 

electronic temperature control or thermostat to call for

 

heat.

8.

Observe the gas supply pressure as all burners are firing.

 

Ensure that inlet pressure is within the specified range.

 

See Connecting To Gas Supply, page 31 for minimum and

 

maximum gas supply pressures.

9.

If gas pressure is out of range, contact gas utility, gas

 

supplier, qualified installer or service agency to determine

 

necessary steps to provide proper gas pressure to the

 

control.

10.

If gas supply pressure is within normal range, turn the

 

power switch to the “OFF” position.

11.

Turn gas valve knobs to the “OFF” position.

12.

Shut off gas supply at the manual gas cock in the gas piping

 

to the unit. If fuel supply is L.P. gas, shut off gas supply at

 

the tank.

Check burner performance by cycling the system while you observe burner response. Burners should ignite promptly. Flame pattern should be stable, see Burner Flames in the Copper-fin2Service Manual. Turn system off and allow burners to cool, then cycle burners again to ensure proper ignition and flame characteristics.

SUPPLYINLET

INLET

PRESSURE

TAP

GASOUTLET

VALVE

CONTROL

KNOB

Figure 3-3_Measuring Gas Supply Pressure at Combination Gas Valve

TABLE - 3D

GAS PIPING SIZE CHART

Nominal

 

 

 

 

Length of Pipe in Straight Feet

 

 

 

 

 

Maximum

Iron Pipe

 

 

 

 

 

 

 

 

 

Capacity of Pipe

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in Thousands of

10

20

30

40

50

60

70

80

90

100

125

150

175

200

Inches

Btu/hr per hour

3/4

369

256

205

174

155

141

128

121

113

106

95

86

79

74

for gas pressures

of 14 Inches

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

697

477

384

328

292

267

246

256

210

200

179

164

149

138

Water Column

1 1/4

1,400

974

789

677

595

543

502

472

441

410

369

333

308

287

(0.5 PSIG) or less

and a pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 1/2

2,150

1,500

1,210

1,020

923

830

769

707

666

636

564

513

472

441

drop of 0.5 Inch

24,100 2,820 2,260 1,950 1,720 1,560 1,440 1,330 1,250 1,180 1,100 974 871 820 Water Column (Based on NAT

2 1/2

6,460

4,460

3,610

3,100

2,720

2,460

2,310

2,100

2,000

1,900

1,700

1,540

1,400

1,300

GAS, 1025 Btu/hr

3

11,200

7,900

6,400

5,400

4,870

4,410

4,000

3,800

3,540

3,300

3,000

2,720

2,500

2,340

per Cubic Foot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of Gas and 0.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

423,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690 7,380 6,870 6,150 5,640 5,130 4,720 Specific Gravity)

Checking gas supply pressure 33 TABLE - 3D

Page 33
Image 33
Lochinvar 2072, 502 Gas connections continued, D, Checking gas supply pressure, Installation & Operation Manual