Installation & Operation Manual
4 Water connections
Install piping from the filter system to the pool heater as shown in the pool heater piping diagrams. See Figures 34 - 38. Minimum pipe diameter to and from the installed pool heater to the filter system piping on models 502 - 752 is 2" and on models 992 - 2072 Btu/hr the minimum is
| 2" NPT |
| WATER |
2" NPT | INLET |
WATER |
|
OUTLET |
|
INSPECTION
PLUGS
Figure 4-1_Water Connections - Models 502 - 752
WATER
INLET
WATER
OUTLET
INSPECTION
PLUGS
TABLE - 4A
Pipe Sizing Chart
502 - 752 Models | Common Pipe Size |
Number of units | (Min.) |
1 | 2" |
2 | 3" |
|
|
3 | 3 1/2" |
|
|
4 | 4" |
|
|
5 | 5" |
|
|
6 | 5" |
|
|
992 - 2072 Models | Common Pipe Size |
Number of units | (Min.) |
1 | 2 1/2" |
|
|
2 | 4" |
|
|
3 | 4" |
|
|
4 | 5" |
|
|
5 | 6" |
|
|
6 | 6" |
|
|
Circulating pump
1.This pool heater is factory supplied with a properly sized pump that circulates water between the pool heater and system.
2.The pump is sized to pool heater input and water hardness. See Water Chemistry on page 45.
3.Lubricate the pump to the manufacturer’s recommendations. Pump damage due to inadequate lubrication is
4.Standard pool heaters are furnished with the following circulating pump mounted in the factory supplied pool loop.
502 - 752 Models
1/4 HP, 120 VAC, 5.8 Amp
992 - 1442 Models
1/2 HP, 120 VAC, 7.4 Amp
1802 - 2072 Models
3/4 HP, 120 VAC, 8.8 Amp
Figure | This pump is sized based on installation of a single pool heater | |||
|
|
|
| |
|
|
|
| in close proximity with the system. If the number of fittings and |
|
|
|
| straight pipe exceeds the quantities shown in this section, a larger |
|
|
|
| pump will be required. As an alternative to changing the pump |
|
|
|
| in these circumstances, the piping can be changed to a |
|
|
|
| Check pump for correct pump rotation. |
| 34 |
|
| The standard pump selection is based on the following pipe and |
|
|
| fittings from the pool heater to the system: | |
|
|