Lochinvar 502, 2072 operation manual Water connections, Installation & Operation Manual, Notice

Models: 2072 502

1 68
Download 68 pages 54.37 Kb
Page 38
Image 38
POOL

Installation & Operation Manual

4 Water connections

Figure 4-7_Multi-stack frame - Cascaded heaters beyond 15 feet of pool piping

MODEL NO

BYPASS PIPE SIZE

CP (N,L) 502-752

2" MIN

CP (N,L) 992-2072

2-1/2" MIN

POOL

RETURN

SENSOR

LOCATION

 

3'

 

MIN

PRIMARY

4" PVC

LOCATION

 

POOL

110°

SUPPLY

SENSOR

LIMIT

 

TO

 

POOL

 

LEADER

MEMBER Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

TABLE 4A

PIPE SIZING CHART

NUMBER

COMMON PIPE SIZE (MIN)

OF UNITS

MODELS 502-752

MODELS 992-2072

1

2"

2-1/2"

2

3"

4"

3

3-1/2"

4"

4

4"

5"

5

5"

6"

6

5"

6"

FROM

POOL

Manual background 4" PVC

FLOWMETER

AUTOMATIC

BYPASS VALVE

RECOMMENDED

ISOLATION

VALVE

COPPER

OR PVC (SEE TABLE)

NOTICE

Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.

Manual background 38 Manual background

Page 38
Image 38
Lochinvar 502, 2072 operation manual Water connections, Installation & Operation Manual, Notice, Pool Return Sensor Location