Lochinvar 2072, 502 operation manual Water connections continued, Installation & Operation Manual

Models: 2072 502

1 68
Download 68 pages 54.37 Kb
Page 37
Image 37
* POOL

Installation & Operation Manual

4 Water connections (continued)

Figure 4-5_Cascaded heaters Within 15 feet of Perpendicular Pool Piping

AUTOMATIC

* POOL

PVC MIN

 

BYPASS VALVE

RETURN

(SEE TABLE)

 

 

SENSOR

 

 

 

SECONDARY

 

 

 

LOCATION

RECOMMENDED

 

 

 

 

 

 

ISOLATION

 

 

 

VALVE

 

 

 

COPPER

 

 

 

OR CPVC

 

 

 

(SEE TABLE)

FROM

 

 

 

POOL

COPPER

 

 

OR CPVC

 

 

(SEE TABLE)

 

 

 

 

110°

 

 

LIMIT

 

 

3'

 

 

MIN

 

TO

 

 

POOL

 

 

 

REQUIRED

 

 

POOL

 

 

RETURN

 

 

SENSOR

MODEL NO

BYPASS PIPE SIZE

LOCATION

 

CP (N,L) 502-752

2" MIN

 

CP (N,L) 992-2072

2-1/2" MIN

 

VALVE

 

POOL RETURN SENSOR

 

 

PRIMARY LOCATION

*NOTE: IF THE RETURN SYSTEM SENSOR IS LOCATED IN THE SECONDARY LOCATION SHOWN ON THE PIPING DIAGRAM, THE UNIT PUMP MUST RUN CONTINUOUSLY TO ENSURE THE WATER FLOW PAST THE SENSOR IS MAINTAINED.

Figure 4-6_Cascaded Heaters Beyond 15 feet of Pool Piping

* POOL

RETURN

SENSOR SECONDARY LOCATION

3'

MIN

110°

LIMIT

REQUIRED

POOL

RETURN

SENSOR TO

LOCATION POOL

COPPER OR PVC (SEE

TABLE)

MODEL NO

BYPASS PIPE SIZE

CP (N,L) 502-752

2" MIN

CP (N,L) 992-2072

2-1/2" MIN

AUTOMATICFROM

BYPASSPOOL

VALVE

POOL RETURN SENSOR PRIMARY LOCATION

4" PVC

FLOWMETER

3" PVC

RECOMMENDED

ISOLATION

VALVE

*NOTE: IF THE RETURN SYSTEM SENSOR IS LOCATED IN THE SECONDARY LOCATION SHOWN ON THE PIPING DIAGRAM, THE UNIT PUMP MUST RUN CONTINUOUSLY TO ENSURE THE WATER FLOW PAST THE SENSOR IS MAINTAINED.

NOTICE Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.

Manual background 37 Manual background

Page 37
Image 37
Lochinvar 2072, 502 operation manual Water connections continued, Installation & Operation Manual