Lochinvar 502, 2072 operation manual Operating information, Status Display Screens cont’d

Models: 2072 502

1 68
Download 68 pages 54.37 Kb
Page 56
Image 56
Status Display Screens (cont’d)

Installation & Operation Manual

7 Operating information

Status Display Screens (cont’d)

By using the Previous/Next (, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the 11 display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display:

Screen #

Display shows:

Description

 

 

The system return sensor acts as the control sensor. The control

 

SYSRTN: ***F (***)

will display the system return temperature as well as the set point in

Screen #3

 

parenthesis.

Line 2

SYSRTN: OPEN

The control does not detect the system return sensor.

 

 

 

 

SYSRTN: SHORTED

The system return sensor wires or the sensor itself has become shorted.

 

 

 

Press the Next arrow key on the SMART SYSTEM display to access Screen #4.

N/A

Press the Next arrow key on the SMART SYSTEM display to access Screen #5.

Screen #5

Line 2

STG DEMAND: ****

The control displays the number of stages firing, based upon demand.

Press the Next arrow key on the SMART SYSTEM display to access Screen #6.

Screen #6

FAN SPEED: ***

The control will display either OFF, LOW, or HIGH depending upon

 

Line 1

fan speed requirements of number of stages firing.

 

 

 

 

 

 

 

Screen #6

0 – 10V RATE: **.*V

The control will display 0 to 10 volts based upon fan speed and unit

 

Line 2

capacity.

 

 

 

 

 

 

 

Press the Next arrow key on the SMART SYSTEM display to access Screen #7.

Screen #7

Line 1

PH CFH: ***

The control will display either ON or OFF based upon a demand (call for heat) for heat.

Press the Next arrow key on the SMART SYSTEM display to access Screen #8.

Screen #8

Line 1

SYS PUMP: ***

The control will display either ON or OFF based upon system pump requirements upon demand.

Press the Next arrow key on the SMART SYSTEM display to access Screen #9.

Screen #9

Line 1

UNIT PUMP: ***

The control will display either ON or OFF based upon unit pump

requirements upon demand.

 

 

 

UNIT PUMP: DELAY

The control will display delay in unit pump operation after the heat

requirements have been satisfied.

 

 

 

Press the Next arrow key on the SMART SYSTEM display to access Screen #10.

Screen #10

FLM SIG – A: **.* µA

The control displays the igniter flame signal of igniter A in microamps.

 

Line 1

 

 

 

 

Screen #10

FLM SIG – B: **.* µA

The control displays the igniter flame signal of igniter B in microamps.

 

Line 2

 

 

 

 

Press the Next arrow key on the SMART SYSTEM display to access Screen #11.

Screen #11

IGN * AMPS: *.* A

The control displays the current of either igniter A or B.

Line 1

 

 

Screen #11

MIX VAL POS: ** %

The control displays the mixing valve percentage open to the system.

Line 2

 

 

 

 

 