1 Determine unit location

1 Determine unit location

Location of unit

This unit meets the safe lighting performance criteria with the gas manifold and control assembly provided, as specified in the ANSI standards for gas-fired units and ANSI Z21.10.3/ CSA 4.3 - latest edition.

1.

Maintain all clearances from combustible construction

 

when locating appliance. See Clearances from Combustible

 

Construction, this page.

2.

Locate the appliance so that if water connections should

 

leak, water damage will not occur. When such locations

 

cannot be avoided, it is recommended that a suitable

 

drain pan, adequately drained, be installed under the unit.

 

The pan must not restrict combustion airflow. Under no

 

circumstances is the manufacturer to be held responsible

 

for water damage in connection with this unit, or any of its

 

components.

3.

The appliance must be installed so that the ignition

 

system components are protected from water (dripping,

 

spraying, rain, etc.,) during appliance operation and service

 

(circulator replacement, control replacement, etc.,).

4.

Appliances located in a residential garage and in adjacent

Installation & Operation Manual

Right Side

3"

(7.5 cm)

Rear

3"

(7.5 cm) (3" min. from any surface)*

Left Side

6" (15 cm) (24" (0.61 m) suggested for

 

service)

Front

Alcove* (30" (0.76 m) suggested for service)

Top

3"

(7.5 cm)

Flue

1"

(25.4 mm)

Hot Water Pipes 1"

(25.4 mm)

*An Alcove is a closet without a door. Thirty-six inches (36") to rear required for outdoor installation.

Note: No additional clearance is needed on the right side of the unit for the observation port. An observation port is located on both the right and left side of the unit.

Figure 1-1_Indoor clearances from combustible construction

spaces that open to the garage and are not part of the living

space of a dwelling unit must be installed so that all burners

and burner ignition devices have a minimum clearance of

not less than 18" (46 cm) above the floor. The appliance

must be located or protected so that it is not subject to

physical damage by a moving vehicle.

5. DO NOT install this appliance in any location where

gasoline or flammable vapors are likely to be present.

6. The appliance must be installed on a level floor.

7. Combustible floor installation:

a. Models 502 - 752 require an approved floor kit for

installation on combustible flooring (reference Table

1A).

b. Models 992 - 2072 are approved for installation

on combustible flooring without a floor kit. Note:

6"

MIN

LEFT

Location of unit SIDE

3"

MIN TOP

30"

MIN

FRONT

3"

MIN

REAR

3"

MIN

RIGHT

SIDE

 

Concrete block over wood flooring is not considered

 

non-combustible.

8.

DO NOT install this appliance directly on carpeting or

 

other combustible material.

9.

Maintain required clearances from combustible surfaces,

 

reference the Indoor Clearances from Combustible

 

Construction Section, this page.

10.

For outdoor models, you must install an optional vent

 

cap. Instructions for mounting the vent cap are included

 

in the venting section of this manual. Do not install

 

outdoor models directly on the ground. You must install

 

the outdoor unit on a concrete, brick, block, or other

 

non-combustible pad. Outdoor models have additional

 

special location and clearance requirements. See Outdoor

 

Installation Venting, page 30. A wind proof cabinet

protects the unit from weather.

Indoor clearances from combustible construction

Maintain minimum specified clearances for adequate operation. Allow sufficient space for servicing pipe connections, pump and other auxiliary equipment, as well as the unit. See rating plate for specific service clearance requirements.

NOTICE

Clearances from combustible construction

are noted on the appliance rating plate.

 

TABLE - 1A

 

COMBUSTIBLE FLOOR KITS

Model

 

Kit Number

502

 

CFK3302

652

 

CFK3303

752

 

CFK3304

Freeze protection

Although these units are CSA International design-certified for outdoor installations, such installations are not recommended in areas where the danger of freezing exists. You must provide proper freeze protection for outdoor installations, units installed in unheated mechanical rooms or where temperatures may drop to the freezing point or lower. If freeze protection is not provided for the system, a low ambient temperature alarm is recommended for the mechanical room. Damage to the unit by freezing is non-warrantable.

9