Lopi Direct Vent Freestanding Stove Installation for qualified installers only, Travis Industries

Models: Direct Vent Freestanding Stove

1 42
Download 42 pages 24.45 Kb
Page 16
Image 16
16 Installation (for qualified installers only)

16 Installation (for qualified installers only)

Vent Termination Requirements (see illustration below)

! Venting terminals shall not be recessed into a wall or siding.

AMinimum 9" clearance from any door or window

BMinimum 12" above any grade, veranda, porch, deck or balcony

CMinimum 12" from outside corner walls

DMinimum 12" from inside corner walls

EMinimum 11" clearance below unventilated soffits or roof surfaces Minimum 18" clearance below ventilated soffits

Minimum 6" clearance from roof eaves NOTE: Vinyl surfaces require 24"

Roof

Surface

11” Min.

Roof

6” Min. Eaves

FMinimum 18" clearance below a veranda, porch, deck or balcony (must have two open sides)

GMinimum 48" clearance from any adjacent building

HMinimum 84" clearance above any grade when adjacent to public walkways or driveways NOTE: may not be used over a walkway or driveway shared by an adjacent building

IMinimum 48" clearance from any mechanical air supply inlet

JMinimum 36" clearance above and 48” below and to the sides of non-mechanical air supply inlet

KMinimum 36" from the area above the meter/regulator (vent outlet)

LMinimum 36" from the meter/regulator (vent outlet)

MMinimum 12” above the roof line (for vertical terminations)

NMinimum 24” horizontal clearance to any surface (such as an exterior wall) – for vertical terminations

Manual background E

NManual background

Manual backgroundManual background M

E

A

K

G Manual backgroundManual backgroundManual backgroundManual background A

F

D Manual backgroundManual background C I

L

B

NOTE: Measure clearances to the nearest edge of the exhaust hood.

E

J

H

Use the vinyl siding standoff (#1250) when installing on an exterior with vinyl siding.

Vent termination must not be located where it will become plugged by snow or other material

These clearances meet UMC-1994 and the CNA/CGA-B149 code standards.

Travis Industries

1 0 0 - 0 1 1 4 2

4 0 5 0 1 1 4

Page 16
Image 16
Lopi Direct Vent Freestanding Stove owner manual Installation for qualified installers only, Travis Industries, 1 0 0, 4 0