Lopi Yankee Bay Pellet Insert manual Installation1, Venting the Pellet Stove

Models: Yankee Bay Pellet Insert

1 40
Download 40 pages 38.74 Kb
Page 11
Image 11

Installation1 1

Venting the Pellet Stove

PELLET VENT MUST MAINTAIN A MINIMUM 3" CLEARANCE TO ANY COMBUSTIBLE (INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER).

DO NOT CONNECT THE PELLET VENT TO A VENT SERVING ANY OTHER APPLIANCE OR STOVE.

DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.

Maximum Venting Distance:

Maximum venting height is 33' (maximum horizontal offset is 10')

Use no more than 180° of elbows (two 90° elbows, or two 45° & one 90° elbow, etc.).

Pellet Vent Type

Must be Type "L" vent and/or Type "L" chimney liner.

Use 4" diameter vent.

Installing the Pellet Vent

Pellet vent connections must be sealed airtight with 500° F. RTV silicone and screwed together with at least three sheet metal screws.

.RTV °F 500Silicone

Seal each vent section (including adapters, elbows, etc...) by injecting a liberal amount of 500° F. RTV silicone into the gap between sections.

The exhaust quick- connect can be removed to allow for installation and cleaning.

Pellet Vent Termination

Termination must be a minimum 6" above the top of the chimney (NOTE: the chimney must meet local codes for height above the roof or other obstructions).

Must have an approved cap (to prevent water from entering).

Must not be located where it will become plugged by snow or other material.