Macurco DVP-120 2.3Main power Connection, 2.4Remote Sensor Connection, 1Main Power Connections

Models: DVP-120

1 37
Download 37 pages 45.49 Kb
Page 10
Image 10
2.3Main power Connection

2.3Main power Connection

The main power cable should be routed into the bottom left conduit entry.

Macurco recommends a minimum wire size of AWG18. The modular connector will accept wire from 12 to 24 AWG.

The safety ground wire should be secured to the ground stud at the bottom left of the cabinet with the lock washer and nut supplied. Macurco recommends the use of a ring terminal for the ground connection.

Refer to Table 2-1 for DVP-120 power connections.

The line and neutral wires should be stripped 1/4 in. (6.5 mm), insert the wire into the wire cavity of the modular connector and tighten the screw clamp. Ensure that the wire cannot be easily pulled from the connector. Plug the modular connector into J4 on the PCB and ensure that it latches into the header properly.

Signal

Terminal Connection

Line (120/220/240/250 VAC)

J4-3

Neutral

J4-1

Ground

Ground Stud

Table 2-1 Main Power Connections

2.4Remote Sensor Connection

Each remote sensor is connected by a four-wire connection – two wires for DC power and two wires for the 4 – 20 mA loop connection. The sensors are connected to the control panel PCB with modular connectors, two sensors per connector. See Figure 2-1 for a view of a typical sensor connector. Refer to Table 2-2 for wire size recommendations.

n+1 +24 Vdc

n+1 +20ma ILOOP

n+1 ILOOP RET

n+1 +24V RET

n +24 Vdc

n +20ma ILOOP

n ILOOP RET

n +24V RET

CH

CH

CH

CH

CH

CH

CH

CH

1

8

Insert this face of connector

into mating connector on

control circuit board.

Figure 2-1 Sensor Interface Connector

Wire gauge

Maximum Run Length (ft.)

 

(feet)

(meters)

18

500

152

16

800

244

14

1250

381

Table 2-2 Recommended Wire Gauge

Revision 0.07

10

Page 10
Image 10
Macurco DVP-120 2.3Main power Connection, 2.4Remote Sensor Connection, 1Main Power Connections, 2Recommended Wire Gauge