Macurco DVP-120 operating instructions 2.5Relay Connection, 2Relay Connector

Models: DVP-120

1 37
Download 37 pages 45.49 Kb
Page 12
Image 12
2.5Relay Connection

2.5Relay Connection

All poles of the three relays are available at the modular connector J2 (see Figure 2-2 for details). J2 is a 9- position variant of the high voltage modular connector used for power input. Each terminal can accommodate a wire size 12 to 24 AWG.

NC

NO

C

NC

NO

C

NC

NO

C

R1

R1

R1

R2

R2

R2

R3

R3

R3

1

 

 

 

 

 

 

 

9

Insert this face of connector

into mating connector on

control circuit board.

Figure 2-2 Relay Connector

To install the wiring for the relays, disconnect the connector from the header on the PCB. Strip the insulation of each wire back approximately 1/4 in. (6.5 mm), insert the bare wire into the terminal and tighten the screw clamp. Ensure that the wire cannot easily be pulled from the connector.

Note that the panel configuration can designate Relay-1 as an ALARM signal relay. Relay-2 and Relay 3 are general purpose in function.

Refer to Table 2-5 for output signals, connector and terminal assignment for all three relays.

Signal Name

Connector-

Signal Name

Connector-

Signal Name

Connector-

 

Pin Number

 

Pin Number

 

Pin Number

Relay 1 NC

J2-1

Relay 2 NC

J2-4

Relay 2 NC

J2-7

Relay 1 NO

J2-2

Relay 2 NO

J2-5

Relay 2 NO

J2-8

Relay 1 Common

J2-3

Relay 2 Common

J2-6

Relay 2 Common

J2-9

Table 2-5 Relay Interface Signals and Connector Assignments