Macurco 1System Wiring Diagram, Engineer And Architect Specifications, MACURCO DVP-120, coil

Models: DVP-120

1 37
Download 37 pages 45.49 Kb
Page 6
Image 6
ENGINEER AND ARCHITECT SPECIFICATIONS

ENGINEER AND ARCHITECT SPECIFICATIONS

Gas detection and exhaust fan control is provided by a Macurco DVP-120 system. This System will use CM-2B or CM-3 Carbon Monoxide (CO) to current transducers, ND-2 Nitrogen Dioxide to current transducers or GT- 11A Combustible Gas to current transducers. Each transducer will measure the level of the target gas and provide this information to the DVP-120 over a 4-to-20 mA current loop. The Transducers are mounted in a standard 6" x 6" electrical enclosure, and operate on low voltage (24 VDC).

All power and signal connections for the transducers are provided from the DVP-120 control panel, via unshielded four conductor cable. The DVP-120 control panel provides three relays which can be used for ventilation fan control or alarm signaling . These relays (SPDT - Form C) are for pilot duty only, capable of switching 10 amp loads up to 240 VAC .

NOTE:

1.Power connections at the sensor are non-polarized.

2.DVP-120 connections are representative of J7, J8, J10, J11, J13 and J14.

 

 

CM-2B

 

 

 

 

 

 

 

 

GT-11A

 

 

 

 

 

 

 

output

 

 

 

 

 

V

 

 

mA

 

 

 

power

 

 

 

 

 

 

 

 

 

output

power

B

A

 

 

 

 

output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D C -

+

 

 

- +

- +

D C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J7, J8,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J10, J11,

8

 

7

6

5

 

4

3

2

1

 

 

 

 

J13, L14

 

 

 

 

 

 

+24 V RET

 

-I LOOP

+I LOOP

+24 VDC

 

+24 V RET

-I LOOP

+I LOOP

+24 VDC

 

 

 

 

Main Fan Power

 

 

 

 

 

 

 

 

 

 

 

J2

 

 

 

 

 

 

 

 

 

 

 

 

MACURCO DVP-120

 

 

 

 

- Strobe

4

Exhaust Fans

coil

 

 

 

 

 

+ Strobe

3

 

GAS DETECTION AND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENTILATION CONTROL PANEL

 

 

- Horn

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+ Horn

1

 

 

 

 

 

 

 

 

Relay 1

 

 

Relay 2

 

Relay 3

 

 

coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Panel Power

 

 

 

 

 

 

 

 

 

 

120 VAC

 

Gnd

120/250 VAC

N.C.

 

N.O.

COM

N.C.

N.O.

COM

N.C.

N.O.

COM

STARTER RELAYS

 

N

 

L

 

ALARM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120 VAC COILS

J4

1

 

3

1

 

2

3

4

5

6

7

8

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J2

120 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Typical coverage for a CO sensor is 5000 sq. ft., 900 sq. ft. for combustible gasses. Extra sensors may be needed near areas where people work, such as toll booths.

2.Macurco provides only the control panels and sensors. Fans, relays, and other devices are provided by the contractor.

3.See the appropriate building code for the size of fans and air changes per unit of time.

exhaust fan

Typical layout in Parking Garage

Air inlet:

 

 

door, damper,

 

 

louvier

DVP-120

 

 

panel

 

 

CM-2B,

CM-2B,

CM-2B,

CM-3 or

CM-3 or

CM-3 or

SS102HC-1

SS102HC-1

SS102HC-1

 

space sensors equally,

 

 

mount 5 feet above floor

 

 

 

Air inlet:

exhaust fan

 

door, damper,

 

louvier

 

 

Figure 1-1 System Wiring Diagram

Revision 0.07

6

Page 6
Image 6
Macurco 1System Wiring Diagram, Engineer And Architect Specifications, MACURCO DVP-120, Gas Detection And, Exhaust Fans