Macurco DVP-120 operating instructions 2.6Horn & Strobe Connection, 3Horn & Strobe Connector

Models: DVP-120

1 37
Download 37 pages 45.49 Kb
Page 13
Image 13
2.6Horn & Strobe Connection

2.6Horn & Strobe Connection

The external horn and strobe connections are available at the modular connector J5 (see Figure 2-3 for details). J5 as a 4-position connector, similar to the sensor interface connectors.

Strobe -

Strobe +

Horn -

Horn +

1

4

Insert this face of connector

into mating connector on

control circuit board.

Figure 2-3 Horn & Strobe Connector

To install the wiring for the horn or strobe, disconnect the connector from the header on the PCB. Strip the insulation of each wire back approximately 0.25 in. (6 mm), insert the bare wire into the terminal and tighten the screw clamp. Ensure that the wire cannot easily be pulled from the connector.

When all wires are connected, seat the modular connector into the PCB header; ensure that the latch engages.

Refer to Table 2-6 for signals, connector and terminal assignment for the horn and strobe.

Signal Name

Connector-Pin

Signal Name

Connector-Pin

 

Number

 

Number

Horn +

J5-1

Strobe +

J5-3

Horn -

J5-2

Strobe -

J5-4

Table 2-6 Horn & Strobe signals and Connector Assignments

Refer to Table 2-7 for recommended wire gauge vs. run length for the horn & strobe functions (maximum 2.5 volt drop in the wire).

Wire gauge

Maximum Run Length (ft.)

(feet)

(meters)

 

24

200

61

22

340

103

20

480

147

18

850

215

Table 2-7 Wire gauge for Horn & Strobe functions

Revision 0.07