![2.6Horn & Strobe Connection](/images/new-backgrounds/55948/5594825x1.webp)
2.6Horn & Strobe Connection
The external horn and strobe connections are available at the modular connector J5 (see Figure
Strobe - | Strobe + | Horn - | Horn + |
1 | 4 |
Insert this face of connector
into mating connector on
control circuit board.
Figure 2-3 Horn & Strobe Connector
To install the wiring for the horn or strobe, disconnect the connector from the header on the PCB. Strip the insulation of each wire back approximately 0.25 in. (6 mm), insert the bare wire into the terminal and tighten the screw clamp. Ensure that the wire cannot easily be pulled from the connector.
When all wires are connected, seat the modular connector into the PCB header; ensure that the latch engages.
Refer to Table
Signal Name | Signal Name | ||
| Number |
| Number |
Horn + | Strobe + | ||
Horn - | Strobe - |
Table
Refer to Table
Wire gauge | Maximum Run Length (ft.) | ||
(feet) | (meters) | ||
| |||
24 | 200 | 61 | |
22 | 340 | 103 | |
20 | 480 | 147 | |
18 | 850 | 215 |
Table 2-7 Wire gauge for Horn & Strobe functions
Revision 0.07 | 13 |