Macurco DVP-120 operating instructions 1INTRODUCTION, 1.1General Information, 1.2Features

Models: DVP-120

1 37
Download 37 pages 45.49 Kb
Page 5
Image 5

1INTRODUCTION

1.1General Information

The DVP-120 Gas Detection and Ventilation Control Panel is a microcomputer based control panel used to operate ventilation fans based on the inputs from remotely mounted gas transducers. The unit is fully tested prior to leaving the factory, and is ready for operation after the wiring is complete and the user system configuration is entered.

System wiring includes the main power connection for the DVP-120, current loop and power connections between the remote sensors and the DVP-120, the fan control connections and/or alarm connections from the DVP-120 to the building ventilation and automation systems. Refer to Figure 1-1 for a representative system- wiring diagram.

The system configuration is entered by the user through the LCD display and keypad. Refer to Figure 1-2 for equipment locations. The system display provides the user with the system status, and the status of each configured sensor. In addition, all control functions of the DVP-120 may be accessed through the system display and keypad.

1.2Features

Twelve analog (current loop) input channels

Three 16A, 240 VAC SPDT fan/alarm relays

Drivers for external Horn and Strobe

Externally visible system, alarm and relay status indicators

Externally visible LCD display showing the status of each transducer and relay

External keypad for user selection of the transducer/alarm display and setting the configuration (password protected)

Up to three ventilation control zones can be defined

Each zone can be controlled based on transducer signals and/or time of day

Each relay is configurable for delay before activation and minimum on time

Fail safe operation can be implemented

Lockable Nema 1 type enclosure

Modular input and output connectors

1.3Compatible Macurco Transducers

Carbon Monoxide (CO):

CM-2B – Solid State sensor with local concentration display (ppm)

CM-3 – Electrochemical sensor with local concentration display (ppm) Nitrogen Dioxide (NO):

ND-2 – Electrochemical sensor with local concentration display (ppm) Combustible Gasses (EX):

GT-11A – Solid State Sensor

Revision 0.07

5

Page 5
Image 5
Macurco DVP-120 1INTRODUCTION, 1.1General Information, 1.2Features, 1.3Compatible Macurco Transducers