1.4 | Specifications1 |
|
|
| – Size: | 10” x 12” x 2” (254 mm x 305 mm x 51 mm) | |
| – Weight: | TBD | |
| – Enclosure: | Nema 1 equivalent steel | |
| – Operating Temperature: | 0° to 50 °C | |
| – Operating Humidity: | 0% to 95% RH | |
| – Power Input: | 100 – 240 VAC, 1 Amp, 47 – 63 Hz, single phase | |
| – Relay Rating (3): | SPDT, 120/240 VAC, 16 A resistive | |
| – LCD Display: | 2 rows of 16 characters with backlight | |
| – Status Indicators (LED): | Power, ALARM/warning, Silenced, Relay 1, Relay 2 & Relay 3 | |
| – Audible indicator: | Internal buzzer, 90 dbA at 1ft | |
| – External Drivers (2): | 24VDC, maximum 250 mA | |
| – CO Transducer Range: | 0 | – 250PPM |
| – NO Transducer Range: | 0 | – 9.0 PPM |
| – EX Transducer Range: | 0 | – 10,000 PPM |
| – Relay On Delay: | 0 | – 15 minutes in 1 second increments |
| – Relay Off Delay: | 0 | – 15 minutes in 1 second increments |
1.5 | Warranty |
|
|
The
THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE ARE LIMITED TO A PERIOD OF TWO (2) YEARS FROM THE PURCHASE DATE.
Macurco shall not be liable for any incidental or consequential damages for breach of this or any other warranty express or implied, arising out of or related to the use of the control panel. Manufacturer or its agent’s liability shall be limited to replacement or repair as set forth above. Buyer’s sole and exclusive remedies are return of the goods and repayment of the price, or repair and replacement of
1.6Return Instructions
Call (303)
Aerion Technologies Inc.
6555 S. Kenton St., Ste 304
Centennial, CO
USA 80111
1Macurco reserves the right to modify or change the specifications of all products without prior notification to the user.
Revision 0.07 | 8 |