Macurco DVP-120 operating instructions Specifications1, Warranty, 1.6Return Instructions

Models: DVP-120

1 37
Download 37 pages 45.49 Kb
Page 8
Image 8
Specifications1

1.4

Specifications1

 

 

 

– Size:

10” x 12” x 2” (254 mm x 305 mm x 51 mm)

 

– Weight:

TBD

 

– Enclosure:

Nema 1 equivalent steel

 

– Operating Temperature:

0° to 50 °C (-32 to 122 °F)

 

– Operating Humidity:

0% to 95% RH non-condensing

 

– Power Input:

100 – 240 VAC, 1 Amp, 47 – 63 Hz, single phase

 

– Relay Rating (3):

SPDT, 120/240 VAC, 16 A resistive

 

– LCD Display:

2 rows of 16 characters with backlight

 

– Status Indicators (LED):

Power, ALARM/warning, Silenced, Relay 1, Relay 2 & Relay 3

 

– Audible indicator:

Internal buzzer, 90 dbA at 1ft

 

– External Drivers (2):

24VDC, maximum 250 mA

 

– CO Transducer Range:

0

– 250PPM

 

– NO Transducer Range:

0

– 9.0 PPM

 

– EX Transducer Range:

0

– 10,000 PPM

 

– Relay On Delay:

0

– 15 minutes in 1 second increments

 

– Relay Off Delay:

0

– 15 minutes in 1 second increments

1.5

Warranty

 

 

The DVP-120 Gas Detection and Ventilation Control Panel is warranted to be free from defective material and workmanship for a period of two (2) years from the date of manufacture (stamped on the unit). If any component becomes defective during the warranty period, it will be replaced or repaired free of charge, if the unit is returned in accordance with the instructions below. This warranty does not apply to units that have been altered or had repair attempted, or that have been subjected to abuse, accidental or otherwise. The above warranty is in lieu of all other express warranties, obligations, or liabilities.

THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE ARE LIMITED TO A PERIOD OF TWO (2) YEARS FROM THE PURCHASE DATE.

Macurco shall not be liable for any incidental or consequential damages for breach of this or any other warranty express or implied, arising out of or related to the use of the control panel. Manufacturer or its agent’s liability shall be limited to replacement or repair as set forth above. Buyer’s sole and exclusive remedies are return of the goods and repayment of the price, or repair and replacement of non-conforming goods or parts. (The Uniform Commercial Code applicable in the State of Colorado shall govern)

1.6Return Instructions

Call (303) 781-4062 for a Return Authorization form. Then carefully pack the control panel with a written description of the nature of the return. Send the unit to the following address:

Aerion Technologies Inc.

6555 S. Kenton St., Ste 304

Centennial, CO

USA 80111

1Macurco reserves the right to modify or change the specifications of all products without prior notification to the user.

Revision 0.07