3.3.3.4 Warning Set Point
|
| S e n s o r 0 1 | C O | |
|
| W a r n i n g : _ _ 5 0 p p m | ||
|
| Figure | ||
The default warning levels for the sensors are: |
| |||
– | Carbon Monoxide | 50 ppm |
| |
– | Nitrogen Dioxide | 3.0 ppm |
| |
– | Combustible | 2,000 ppm (5% LEL for methane) |
Setting a warning level of 0 (zero) will disable warning detection for this particular sensor.
3.3.3.5 Range
S e n s o r | 0 1 | C O |
R a n g e : |
| _ 2 0 0 p p m |
Figure 3-28 Sensor’s Range
The range for each sensor is the gas concentration that corresponds to the 20 mA signal level.
The default range values for the sensors are: |
| |
– | Carbon Monoxide | 200 ppm |
– | Nitrogen Dioxide | 6.0 ppm |
– | Combustible | 10,000 ppm (25% LEL for methane) |