3.3.7.7 Rising Trip Point
|
| Z 1 G r o u p 1 | N O 2 | |
|
| R i s i n g : | 2 . 5 p p m | |
|
| Figure | ||
The default rising trip points are: |
|
| ||
– | Carbon Monoxide | 100 ppm |
| |
– | Nitrogen Dioxide | 2.5 ppm |
| |
– | Combustible | 2,000 ppm |
| |
3.3.7.8 Falling Trip Point |
|
|
|
|
|
|
|
| |
|
| Z 1 G r o u p 1 | N O 2 | |
|
| F a l l i n g : | 1 . 0 p p m | |
|
| Figure | ||
The default falling trip points are: |
|
| ||
– | Carbon Monoxide | 50 ppm |
| |
– | Nitrogen Dioxide | 1.2 ppm |
| |
– | Combustible | 1,000 ppm |
|
3.3.7.9 Multiple Sensor Mode
Z 1 | G r o u p 1 | N O 2 |
M o d e : 2 V o t i n g |
Figure
When multiple sensors are being monitored by a group the output decision can be based on either voting, as shown here, or the average of all sensors in the group. Valid modes are:
– | 1 | Average |
– | 2 | Voting |
When the configuration is Average, the gas concentrations from all sensors in the group are averaged and if the average is greater than or equal to the rising trip point the zone outputs(s) are activated. When the average is less than or equal to the falling trip point the zone output(s) are
When the configuration is Voting, the number of sensors in the group indicating a value greater than or equal to the rising trip point is counted. If the count is greater than or equal to the quorum then the zone output(s) are activated. If the count of sensors indicating less than or equal to the falling trip point is greater than or equal to the quorum the zone output(s) are
3.3.7.10 Multiple Sensor Quorum
Z 1 | G r o u p 1 | N O 2 |
Q u | o r u m : _ 2 |
|
Figure
It is up to the installer to ensure that the quorum entry is appropriate for the configuration. Valid entries are one to twelve, but a value greater than the number of sensors being monitored by the group, stops the group from controlling the outputs.
Revision 0.07 | 31 |