Majestic Appliances DVB4136 manual Twist Lock Pipes, How to Use the Vent Graph, 20012322

Models: DVB4136

1 52
Download 52 pages 13.38 Kb
Page 15
Image 15
Twist Lock Pipes

Twist Lock Pipes

When using twist lock pipe it is not necessary to use sealant on the joints. The only areas of the venting system that need to be sealed with high temperature silicone sealant are the sliding joints of any telescopic vent section used in the system.

To join twist lock pipes together, simply align the beads of the male end with the grooves of the female end, twisting the pipe until the flange on the female end contacts external flange on the male end. It is recom- mended that you secure the joints with three (3) sheet metal screws, however, this is not mandatory with twist lock pipe. (Fig. 17)

To make it easier to assembly the joints, we suggest putting a lubricant (Vaseline or similar) on the male end of the twist lock pipe prior to assembly.

Male End

Female End

 

Screw Holes

TWL100

 

 

Fig. 17

Twist-lock pipe joints.

 

How to Use the Vent Graph

The Vent Graph should be read in conjunction with the following vent installation instructions to determine the relationship between the vertical and horizontal dimen- sions fo the vent system.

1.Determine the height of the center of the horizontal vent pipe exiting through the outer wall. Using this dimension on the Sidewall Vent Graph (Fig. 18), locate the point intersecting with the slanted graph line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.Select the indicated dimension, and position the fireplace in accordance with same.

EXAMPLE A:

If the vertical dimension from the floor of the unit is 11’ (3.4 m) the horizontal run to the face of the outer wall must not exceed 14’ (4.3 m).

EXAMPLE B:

If the vertical dimension from the floor of the unit is 7’ (2.1m), the horizontal run to the face of the outer wall must not exceed 8¹⁄₂’ (2.6 m).

DVB4136 Direct Vent Gas Fireplace

 

 

30

 

 

 

29

 

 

 

28

 

 

 

27

 

to

 

26

 

formdimensionthe floor of the unit

horizontaltheofcenter vent pipe

25

 

11

 

 

 

24

 

 

 

23

 

 

 

22

 

 

 

21

 

 

 

20

 

 

 

19

 

 

 

18

 

 

 

17

 

 

 

16

 

 

 

15

 

 

 

14

 

 

 

13

 

Vertical

the

12

eg: A

8

 

 

 

10

 

 

 

9

 

7

eg: B

6

 

5

 

4

 

3

 

34 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Horizontal dimension from the outside face of the

wall to the center of the fireplace vent flange

Fig. 18 Sidewall venting graph. (Dimensions in feet)

Refer to Page 20 for venting requirements for snor- kels.

Rear Wall Vent Application

When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind the appliance.

Only CFM Corporation venting components are approved to be used in these applications (See ‘Venting Components’ listed for different installation requirements).

The maximum horizontal distance between the rear of the appliance (or end of the transition elbow in a corner application) and the outside face of the rear wall is 20” (508 mm). (Fig. 19, 20)

Only one 45° elbow is allowed in these installations.

Minimum clearances between vent pipe and com- bustible materials are as follows:

Top - 2” (51 mm) Sides - 1” (25 mm)

Bottom - 1” (25 mm)

20012322

15

Page 15
Image 15
Majestic Appliances DVB4136 manual Twist Lock Pipes, How to Use the Vent Graph, Rear Wall Vent Application, 20012322