Setpoint Profiler

How to start a profiler

A profiler can be started from the Ready, Hold or End state.

Table 5-13 Profiler Starting Procedure

Step

Action

SP1

Result/Notes

 

 

is displayed.

 

PROFIL01

 

1 Press Display button until the Setpoint Trend

 

 

 

 

500.00

 

 

PV

0.00

0:00:00

0.00

 

 

 

 

 

SP

0.00

SEG1/9

READY

 

 

 

 

 

2 Press Tab button to display the profile menu.

SP1

PROFIL01

500.00

 

 

 

 

 

 

 

START

 

 

 

 

 

 

HOLD

 

 

 

 

 

 

RESET

 

 

 

 

 

 

ADVANCE

 

 

 

 

 

 

SHUTDOWN

 

 

 

 

 

 

EVENTS

 

 

 

 

 

 

DETAIL

 

 

 

 

 

 

SUMMARY

 

 

 

 

 

 

EDIT

 

 

 

 

 

 

LOAD

 

 

 

 

 

 

 

 

 

0.00

 

 

 

PV

0.00

 

 

 

 

0:00:00

 

 

 

SP

0.00

SEG1/9

READY

 

 

 

 

 

 

 

 

 

 

3

Cursor is on Start. Press Enter.

Profiler starts running at segment #1 if in Ready

 

 

or End or resumes running from its Hold state. If

 

 

in Ready state and Hot Start has been activated,

 

 

profiler will start at the first point in the profile

 

 

where the present value of PV #1 occurs. Event

 

 

outputs assume their states as of the beginning of

 

 

the running segment. Profiler status on lower

 

 

right of display indicates RUN after you start the

 

 

profiler.

 

 

 

 

 

ATTENTION

A profile can also be started by pressing the F1 button, but only if that profile’s START parameter was configured as SY1 F1. See Section 5.4.