Programming Function Blocks and Features

 

 

 

 

Table 4-8 Loop Characteristics (continued)

 

 

 

 

 

 

 

 

Characteristic

 

 

What to be aware of

 

 

Split output programming

 

 

A splitter output type (Standard or Advanced) calculated value is used to send

 

 

requirements

 

 

the Split loop output to 2 or 3 different analog output (AO) functions. In this

 

 

 

 

 

case, program the control loop to receive a feedback from the back calculation

 

 

 

 

 

output of the splitter calculated value. In other words, loop Feedback = CVn BC

 

 

 

 

 

(where CVn is a Splitter type calculated value and BC is its output).

 

 

 

 

 

Program the splitter calculated value to accept the back-calculation values (BC)

 

 

 

 

 

of each analog output function block (AO) as its feedback source. In other

 

 

 

 

 

words, CVn FB = AOn BC.

 

 

 

 

 

 

 

Cascade primary loop

 

Be sure to scale the cascade primary loop’s output limits to match the process

 

 

 

 

 

variable range of the secondary control loop. (Note: Output scaling is only

 

 

 

 

 

available on the cascade primary type of control loop.) The primary loop

 

 

 

 

 

feedback should be connected to the back calculation value of the secondary

 

 

 

 

 

control loop.

 

 

 

 

 

 

 

 

Miscellaneous loop

 

 

Other parameters affecting loops are latching and reset limit. These are

 

 

characteristics

 

 

described in the loop prompt table.

 

 

 

 

 

 

 

Programming Procedure

To program Control Loops, select "PROGRAM CONTROL LOOPS" in the Main Program Menu. Select a loop to program.

Table 4-9 illustrates the menu selections for the various loop types. See Table 4-10 for an alphabetical listing of these parameters’ descriptions. Enter all desired choices, then repeat the procedure, if desired, for the other Loops.

Video Recorder – User Manual

91

Page 105
Image 105
Honeywell VRX180 user manual Programming Procedure