Setpoint Profiler

Editing Segments

Use the following prompts to map out each segment’s value, time, and events. Up to 63 segments are programmable per profile.

Table 5-6 Edit Segments Prompts

Prompt

 

 

Range/Selections

 

 

 

Definition

 

NEXT SEGMENT

 

 

 

 

 

 

Select this to edit the next segment.

 

 

 

 

 

 

 

 

 

 

PREVIOUS SEGMENT

 

 

 

 

 

 

Select this to edit the previous segment

 

 

 

 

 

 

 

 

 

VALUE

 

 

OFF or number

 

 

This prompt is active for soak segments

 

 

 

 

 

 

 

 

and value/duration ramp types. Enter the

 

 

 

 

 

 

 

 

value of the segment.

 

 

 

 

 

 

 

 

 

AUX VALUE

 

 

OFF or number

 

 

This value is an auxiliary soak output of

 

 

 

 

 

 

 

 

the profile. The output is identified as

 

 

 

 

 

 

 

 

SPn A1 and remains constant for the

 

 

 

 

 

 

 

 

duration of the segment.

 

 

 

 

 

 

 

 

 

TIME

 

 

OFF or Positive number

 

 

The purpose of the number entered here

 

 

 

 

 

 

 

 

depends on the ramp type of the profile.

 

 

 

 

 

 

 

 

See 4 types of ramp segments on page

 

 

 

 

 

 

 

 

178 for details.

 

 

 

 

 

 

 

 

 

GUAR SOAK #1

 

 

ON or OFF

 

 

ON means the profiler will Hold during this

 

 

 

 

 

 

 

 

segment if deviation between PV #1 and

 

 

 

 

 

 

 

 

the profiler output exceeds the

 

 

 

 

 

 

 

 

guaranteed soak limits in Table 5-5. OFF

 

 

 

 

 

 

 

 

means the profiler will not Hold during this

 

 

 

 

 

 

 

 

segment due to deviation. See

 

 

 

 

 

 

 

 

Guaranteed Soak on page 182 for details.

 

 

 

 

 

 

 

 

 

GUAR SOAK #2

 

 

ON or OFF

 

 

ON means the profiler will Hold during this

 

 

 

 

 

 

 

 

segment if deviation between PV #2 and

 

 

 

 

 

 

 

 

the profiler output exceeds the

 

 

 

 

 

 

 

 

guaranteed soak limits in Table 5-5. OFF

 

 

 

 

 

 

 

 

means the profiler will not Hold during this

 

 

 

 

 

 

 

 

segment due to deviation. See

 

 

 

 

 

 

 

 

Guaranteed Soak on page 182 for details.

 

 

 

 

 

 

 

 

 

EDIT EVENTS

 

 

EVENT #1

 

 

Enter the state of up to 16 discrete

 

 

 

.

 

 

 

outputs of this segment. These outputs

 

 

 

 

 

 

can be used to trigger any action requiring

 

 

 

.

 

 

 

 

 

 

 

 

 

a discrete signal, such as a relay or

 

 

 

.

 

 

 

another function block.

 

 

 

 

 

 

An event stays on or off for the entire

 

 

 

 

EVENT #16

 

 

 

 

 

 

 

 

segment.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To trigger events in the middle of a

 

 

 

 

 

 

 

 

segment, you must divide the segment

 

 

 

 

 

 

 

 

into 3 segments. See Segment Events on

 

 

 

 

 

 

 

 

page 183 for details.

 

 

 

 

 

 

 

 

 

 