Diagnostic and error messages

Table 9-4 Error Messages (continued)

 

Error

 

 

Description

 

 

User Action

 

 

 

 

 

 

 

 

 

 

 

Low Limit Outside of

 

 

AI circuit low limit is < voltage limit of -500 mV.

 

 

Change circuit low limit to > -500

 

 

Circuit

 

 

 

 

 

mV.

 

 

 

 

 

 

 

 

 

 

 

Low limit Outside of

 

 

For thermocouple or RTD, Range Low limit is < the

 

 

Change limit to within specified

 

 

Table

 

 

low limit for that type.

 

 

limits for that type. (Table 4-3)

 

 

 

 

 

 

 

 

 

 

 

Low Output Limit less

 

 

A current output (CAT) low limit is less than zero.

 

 

Change current output (CAT) low

 

 

than Zero

 

 

 

 

 

limit to greater than or equal to

 

 

 

 

 

 

 

 

zero.

 

 

 

 

 

 

 

 

 

 

 

Monthly Periods Must Be

 

 

Periodic Timer CV period is monthly but no phase is

 

 

Change Periodic Timer phase.

 

 

Phased

 

 

defined.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No Room for Function

 

 

System has used all allocated function blocks.

 

 

Verify programming of affected

 

 

Block

 

 

 

 

 

function block.

 

 

 

 

 

 

 

 

 

 

 

Number of Frames Out of

 

 

Rolling Average CV # of Samples is less than 1 or

 

 

Change # of Samples to 1-60.

 

 

Range

 

 

greater than 60.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Out of EEPROM Memory

 

 

No more static memory or EEPROM memory.

 

 

Verify programming of affected

 

 

 

 

 

 

 

 

function block.

 

 

 

 

 

 

 

 

 

 

Out of RAM Memory

 

No more RAM available.

 

 

Verify programming of affected

 

 

 

 

 

 

 

 

function block.

 

 

 

 

 

 

 

 

 

 

 

Output Limits Equal

 

 

Output (range) limits (low and high) must be unequal.

 

 

Change to unequal limits

 

 

 

 

 

 

 

 

 

 

 

Pairs Inconsistent

 

 

Applies to custom AI or Function Generator CV.

 

 

Program a Y for each X or vice

 

 

 

 

 

Curve has Xn but no Yn or vice versa. Curve does

 

 

versa. Program at least 2 X’s and

 

 

 

 

 

not have at least 2 X,Y pairs.

 

 

2 Y’s.

 

 

 

 

 

 

 

 

 

 

 

Request Made with

 

 

Probably caused by someone incorrectly editing the

 

 

Verify programming of affected

 

 

Invalid Tag

 

 

configuration file or by a corrupt .LNC file.

 

 

function block.

 

 

 

 

 

 

 

 

 

 

Requires a Deviation

 

 

Deviation alarm does not contain deviation.

 

Program alarm with deviation.

 

 

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Requires Input

 

 

Alarm does not contain an input.

 

Program alarm with input.

 

 

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Requires Setpoint

 

 

Alarm does not contain a setpoint.

 

Program alarm with a setpoint.

 

 

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RJ Not in Curve

 

 

AI is custom type, class thermocouple, RJ enabled

 

 

Y values must contain 0-65

 

 

 

 

 

but curve does not contain 0-65 degrees C (32-149

 

 

degrees C (32-149 degrees F).

 

 

 

 

 

degrees F).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature Constant

 

 

F0 Sterilization CV Temperature constant is not

 

 

Program Temperature constant

 

 

Not Programmed or Less

 

 

programmed or is less than zero.

 

 

with value greater than or equal to

 

 

Than Zero

 

 

 

 

 

zero.

 

 

 

 

 

 

 

 

 

 

 

Temperature Input Not

 

 

F0 Sterilization CV Temperature Input is not

 

 

Program Temperature input with

 

 

Programmed or Less

 

 

programmed or is less than zero.

 

 

value greater than or equal to

 

 

Than Zero

 

 

 

 

 

zero.

 

 

 

 

 

 

 

 

 

 

 

Temperature Reference

 

 

F0 Sterilization CV Reference Temperature is not

 

 

Program Reference Temperature

 

 

Not Programmed or Less

 

 

programmed or is less than zero.

 

 

with value greater than or equal to

 

 

Than Zero

 

 

 

 

 

zero.

 

 

 

 

 

 

 

 

 

 