Setpoint Profiler

How to advance a profiler to the next segment

Table 5-16 Profiler Advance Procedure

 

Step

 

 

Action

 

 

Result/Notes

 

 

1

 

 

Place profiler in Hold.

 

See Profiler Hold procedure inTable 5-14.

 

 

 

 

 

 

 

 

 

 

 

2

 

 

Press Decrement button to move cursor to

 

 

Profiler advances to next segment. Each press of

 

 

 

 

 

Advance. Press Enter.

 

 

Enter advances the profiler one segment. If at

 

 

 

 

 

 

 

 

the last segment, the profiler advances to the first

 

 

 

 

 

 

 

 

segment. If it is a multiphase profile, the profiler

 

 

 

 

 

 

 

 

advances within the batch phase only. Events

 

 

 

 

 

 

 

 

assume their segment states.

 

 

 

 

 

 

 

 

 

 

 

3

 

 

To resume running the profiler, select Start.

 

 

Profile resumes running from the new segment.

 

 

 

 

 

 

 

 

 

 

How to shut down a profiler

Table 5-17 Profiler Shutdown Procedure

 

Step

 

 

Action

 

 

Result/Notes

 

 

1

 

 

Place profiler in Hold by performing Profiler

 

 

See Profiler Hold procedure in Table 5-14.

 

 

 

 

 

holding procedure (Table 5-14).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

Press Decrement button to move cursor to

 

 

Profiler advances to the shutdown phase.

 

 

 

 

 

Shutdown. Press Enter.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

To resume running the profiler, select Start.

 

 

Profile resumes running from the beginning of the

 

 

 

 

 

 

 

 

shutdown phase.

 

 

 

 

 

 

 

 

 

 

204

Video Recorder – User Manual

Page 218
Image 218
Honeywell VRX180 user manual How to shut down a profiler 17 Profiler Shutdown Procedure