Programming Function Blocks and Features

Diagnostics

Data storage for Diagnostics is a complete log of all diagnostic messages. It includes the diagnostic code or identifier message and its time and date of occurrence.

Setup is done with the following parameters: STORAGE MODE, ROLLOVER, DIAG SAMPLES, EXTERNAL ENABLE, SELECT FILENAME. See Table 4-72 for descriptions.

Depending on your selections, data collection will begin when the first diagnostic occurs, or when the first diagnostic occurs after a batch start occurs.

When calibration is executed, the record is time stamped and stored to the diagnostic file. The number of samples which can be stored on a disk (DIAG SAMPLES) can be up to 1600.

Unit Data

Values for up to 12 points (analog input, calculated value, discrete input, discrete output, totalizer, etc.) can be sampled at user-definable intervals and stored on floppy disk. The sample interval must be set by a schedule or triggered by a discrete event. Prompts are described in Table 4-74.

Table 4-74 Unit Data Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

POINTS#1 –

 

 

OFF or analog parameter or

 

 

Enter up to 12 points.

 

 

POINTS#12

 

 

discrete parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STORAGE MODE

 

 

OFF, CONTIN, BATCH, or

 

 

Continuous storage becomes active immediately upon

 

 

 

 

 

ON COMMAND

 

 

initialization. Batch storage is controlled by a discrete

 

 

 

 

 

 

 

 

parameter (see BATCH CONTROL, page 174) or by

 

 

 

 

 

 

 

 

start/stop batch menu item. Batch data may be started and

 

 

 

 

 

 

 

 

stopped several times in a single file until the file is full.

 

 

 

 

 

 

 

 

Batch start increments a batch number that is stored along

 

 

 

 

 

 

 

 

with the data. The batch number may be used for data

 

 

 

 

 

 

 

 

retrieval and analysis using SDA data analysis software.

 

 

 

 

 

 

 

 

ON COMMAND storage collects a single sample of data

 

 

 

 

 

 

 

 

whenever the EXTERNAL ENABLE discrete makes an off-

 

 

 

 

 

 

 

 

to-on transition. If this mode is used, then SET UP

 

 

 

 

 

 

 

 

SCHEDULE is ignored.

 

 

 

 

 

 

 

 

 

 

 

COPY DISPLAY

 

 

 

 

 

Copies the data point list already set up for a currently

 

 

SETUP

 

 

 

 

 

active Unit Data display.

 

 

 

 

 

 

 

 

 

 

 

ROLLOVER

 

 

ON, OFF

 

 

Select ON to continue gathering and storing trend data after

 

 

 

 

 

 

 

 

the Unit data file becomes full. The new data will replace the

 

 

 

 

 

 

 

 

oldest data on the disk as it is collected. No warning will be

 

 

 

 

 

 

 

 

given.

 

 

 

 

 

 

 

 

Select OFF to stop trend storage when trend space

 

 

 

 

 

 

 

 

becomes full. A “DISK FULL” message will then appear.

 

 

 

 

 

 

 

 

Data is buffered until a new disk is inserted and initialized.

 

 

 

 

 

 

 

 

 

 

 

UNIT DATA

 

 

Enter a value from 0-1600

 

 

Number of samples.

 

 

SAMPLES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXTERNAL ENABLE

 

 

OFF, discrete parameter, 0, 1

This discrete parameter will allow Unit data storage when

 

 

 

 

 

 

 

 

ON(1) and will stop Unit data storage when OFF(0). This

 

 

 

 

 

 

 

 

enable is independent of the storage mode; it does not

 

 

 

 

 

 

 

 

control batch start/stop.

 

 

 

 

 

 

 

 

 

 